Operating the Sensor
Setting
item
Bank Setting value/
default value
General description
Offset
value
Y
Set an offset value (value to be added) to the output result display.
When the external input “Offset” setting is set to “ON,” this offset value will be displayed.
-32.767 to +32.767
[
0.00
]
* The unit varies depending on the measurement function.
* You can set this value in steps that are 10 times the value of the minimum
display digit.
Hysteresis
Y
To prevent chattering, set the amount that the value can fall below (or exceed) the threshold before the
output state changes from the state outside the range specified by the thresholds.
0 / 4 / 8 / 16 /
32 / 50 / 75 /
100 / 150 / 200 /
300 / 500 /
750 / 1000 /
1500 /2000
[
0
]
* The unit varies depending on the measurement function.
Offset
Y
A value will be added to or subtracted from the measured value so that the display value equals the
“Offset value” setting.
For example, if the offset value is “0,” the display will be “0” when the offset operation is performed.
When measurement is not possible, offset input will be ignored.
OFF
The offset will be cleared.
ON
The offset operation will be performed.
Reference: For details on the output display settings, see “7.8 Output Settings.”
5.5.2
Output Items (OUTA)
When the OUTA tab is selected, you can use the output display settings
to configure the following items.
Setting
item
Bank Setting value/
default value
General description
Out target
Y
Select the area or calculation to set as the output target.
Area1
The measured result of area 1 will be output.
Area2
The measured result of area 2 will be output.
Area3
The measured result of area 3 will be output.
Area4
The measured result of area 4 will be output.
Calc1
The result of calculation 1 will be output.
Calc2
The result of calculation 2 will be output.
20mA
Y
Set the upper limit of analog output.
-31.767 to +32.767
[
+25.000
]
* The unit varies depending on the measurement function.
4mA
Y
Set the lower limit of analog output.
-32.767 to +31.767
[
-25.000
]
* The unit varies depending on the measurement function.