To allow maximum customization of the controller, the status of all the buttons can be used in
the AND/OR logics or in the PLC, through the following states:
•
ST_304: START key pressed.
•
ST_305: STOP key pressed.
•
ST_306: GCB key pressed.
•
ST_308: MODE_UP button pressed.
•
ST_309: MODE_DOWN button pressed.
•
ST_310: UP key pressed.
•
ST_311: DOWN key pressed.
•
ST_312: LEFT key pressed.
•
ST_313: RIGHT key pressed.
•
ST_314: ENTER key pressed.
•
ST_315: EXIT key pressed.
•
ST_316: SHIFT key pressed.
•
ST_317: ACK button pressed.
LED OFF
LED steady ON
LED flashing
Signalling
Function
PROG. /OFF
Indicates that the operation mode is OFF/RESET
Flashing at 50% on: indicates that you are accessing the
PROGRAMMING menu
The controller is in another operating mode.
MAN.
Indicates that the operation mode is MANUAL
Flashing at 50% on: the controller is in another operating mode.
AUTO
TEST
Indicates that the operation mode is AUTOMATIC
Flashing at 50% on: indicates that the operating mode is TEST
Flashing at 90% on: indicates that the operating mode is
REMOTE START.
The controller is in another operating mode.
ALARM
Indicates the presence of at least one alarm (block) or
deactivation.
Flashing at 50% on: indicates the presence of at least one
warning or one latched warning.
No anomalies.
CAN0
Signals that the CAN-BUS interface is active and in ERROR-
ACTIVE mode.
Flashing at 25% on: signals a communication error. The port is
in ERROR-PASSIVE mode.
Flashing at 75% on: signals a communication error. The port is
in BUS-OFF mode.