216
Technical Handbook
At the end of the document [1] there
is a table that summarize all the anomalies; if in the “Over”
column the character “G” is present, it means that, in presence of the generator protections
override, that anomaly becomes a warning.
In the same way, in the description of the anomalies in this document (chapter 10), for each
of them it
is indicated to which override request it is related: if the text “generator” is specified,
it means that, in presence of the generator protections override, that anomaly becomes a
warning.
See previous paragraph. To activate the complete protection override, an input set by the
function “DIF.2063 – Full override of protections” must be active.
At the end of the document [1]
there is a table that summarize all the anomalies; if in the “Over”
column the character “F” is present, it means that, in presence of the complete protections
override, that anomaly becomes a warning.
In the same way, in the description of the anomalies in this document (chapter 10), for each
of them it is indicated to which override request it is related:
if the text “full” is specified, it
means that, in presence of the complete protections override, that anomaly becomes a
warning.
The controller manages internally the following counters:
•
Controller total power supply time (hours) counter.
•
Counter for engine starts (resettable to zero).
•
Counter for engine working hours (resettable to zero).
•
Counter for engine working hours with GCB closed (resettable to zero).
•
Counter for engine working hours with engine protections override activated
(resettable to zero).
•
Total counter for engine working hours (resettable to zero).
•
Total counter for hours to next service 1.
•
Total counter for hours to next service 2.
Moreover:
•
Number of charge cycles (resettable to zero).
•
Counter for the energy (Ah) transferred to the battery during the charge cycles
(resettable to zero).
•
Counter for the power (Wh) transferred to the battery during the charge cycles
(resettable to zero).
•
Number of discharge cycles (resettable to zero).
•
Counter for the energy (Ah) absorbed from the battery during the discharge cycles
(resettable to zero).
•
Counter for the power (Wh) absorbed from the battery during the discharge cycles
(resettable to zero).
•
Total number of charge cycles.
•
Counter for the total energy (Ah) transferred to the battery during the charge cycles.