Technical Handbook
▪
Lamp off: breaker open.
▪
Blinking lamp (during 25% of time): the controller sent the breaker a 'close' command, yet
it is open.
▪
Blinking lamp (during 75% of time): the controller sent the breaker an 'open' command,
yet it is closed.
The following functions for the configuration of the digital inputs are linked to circuit breakers
management (besides those described for circuit breakers direct controls):
•
DOF.4035: the controller activates this output to signal the presence of at least one
anomaly related to the circuit breakers:
o
013 - ACB not closed.
o
023 - ACB not opened.
o
014 - GCB not closed.
o
024 - GCB not opened.
o
113 - BCB not closed.
o
123 - BCB not opened.
o
114 - LCB not closed.
o
124 - LCB not opened.
The controller records any change of the circuit breakers status in the events log, if enabled
with bit 4 and 5 respectively, of the P.0441 parameter:
•
EVT.1030: Closure command for GCB.
•
EVT.1031: Opening command for GCB.
•
EVT.1032: GCB closed.
•
EVT.1033: GCB opened.
•
EVT.1035: Closure command for ACB.
•
EVT.1036: Opening command for ACB.
•
EVT.1037: ACB closed.
•
EVT.1038: ACB opened.
•
EVT.1430: Closure command for BCB.
•
EVT.1431: Opening command for BCB.
•
EVT.1432: BCB closed.
•
EVT.1433: BCB opened.
•
EVT.1435: Closure command for LCB.
•
EVT.1436: Opening command for LCB.