Function
OFF/RESET
PROGRAM
The generator is disabled; warnings and lockouts are cancelled.
You can program the parameters.
MAN
Gen-set is in manual mode.
Press the
START
button to start the engine.
Press the
STOP
button to stop the engine.
MCB
button and
GCB
button for the manual control of the
commutation/switches in accordance with system SW - HW configuration.
With
BUS
ON, synchronization is required.
AUTO
TEST
Gen-set is in automatic mode: all the functions are controlled automatically. The
combination of the buttons
START
and
MODE
lets you
activate/deactivate the
TEST
mode; the
STOP
button lets you stop the
generator (with a lockout).
Buttons
MCB
and
GCB
let you switchover the devices (only in the
TEST
mode and on the basis of the type and plant configuration).
The activation of a suitably configured external input (or receiving a given
command via SMS or from a serial port) can force the starting of the generator
and the load outlet with the network connected or with the inhibition input on
(
REMOTE START
).