User’s Manual    7

 

Four settings can be adjusted on the device using the trimmers on the front: 

 

TR1 - RAMP:

 adjusts  the  linear  increment  ramp  for  the  value/duration  of  the  command; 

corresponds to the increment/decrement speed of the value with the respective controls enabled. 
Turning clockwise increases the rapidity of the increment, which decreases vice versa counter-
clockwise. The total time of the range can be adjusted from 4 seconds to 120 seconds. 

 

TR2 - RESET

adjusts the value after a RESET command; between MIN and MAX value: 

normally corresponds to 50% of the output (if output is set to +/- 10 mA the reset value is 0 mA) 

 

TR3 - MIN:

 

adjusts the minimum value obtainable with 

DOWN

 command; turning the trimmer 

clockwise increases the minimum value 

 

TR4 - MAX:

  adjusts the maximum value obtainable with the 

UP

 command; the maximum value 

increases as the trimmer is turned clockwise 

To  get  the  full  range, 

MIN

  must  be  turned  fully  counter-clockwise  and 

MAX

  fully  clockwise.  In  the 

abnormal  condition  in  which  the  set 

MIN

  value  exceeds  the  set 

MAX

  value  or  vice  versa;  after  an 

increment or decrement command, the current output remains stable at a fixed value. 

The value range can be adjusted observing the relative position of the trimmers, the limits (minimum and 
maximum) are directly proportional to the angles of rotation of the respective trimmers at the nominal 
value. The RESET trimmer adjusts the default value; the adjustment is linear between the MIN and MAX 
values set (ex. with trimmer in the middle of its range, there is the intermediate value halfway between 
MIN and MAX). 

To adjust the range, proceed as follows: 

-

 

turn RAMP (TR1) to half its value; 

-

 

set the MAX value to half the value  

-

 

set the MIN value to half the value 

Proceed as follows: 

-

 

With  the  UP  input  always  active,  adjust  the  output  to  the  desired  maximum  value  by  turning 

trimmer MAX TR4 clockwise.  

-

 

With the DOWN input always active, adjust the output to the desired minimum value by turning 

trimmer MIN TR3 clockwise. 

-

 

With the RESET input always active, adjust the output to the desired reset value by turning trimmer 

RESET TR2 clockwise/counter-clockwise. 

-

 

Adjust trimmer RAMP (TR1) to obtain the desired rapidity of increment/decrement response.  

To fine tune the trimmer values, use the following register: 

 

40019 

40019 

Select an adjustment 
source 

0  =  from  trimmer,  1  = 
from  Modbus,  2  = 
Modbus  +  trimmer  for 
fine tuning (+/- 12.5%) 

-

 

By setting the registry to 0 the MIN, MAX, RESET, RAMP values are only acquired by the trimmer. 

 

Содержание DIPOT

Страница 1: ...Filename EAAM024505EN docx Rev 05 Date 07 05 2013 ID Document EAAM0245 Product DIPOT...

Страница 2: ...tion 4 2 4 Digital inputs 6 2 5 Analog Inputs 6 2 6 Adjustments 7 3 Voltage isolator mode 8 4 Connections 9 4 1 RS485 interface version connections 10 4 1 1 Modbus addresses and communication protocol...

Страница 3: ...and piloted with UP and DOWN digital inputs or by modifying the Modbus protocol registry value via RS485 connection or CANBUS J1939 connection to our generator management boards DST4601 DST4601PX DST...

Страница 4: ...ng The maximum current absorption is approximately 80 mA at a voltage of 10V The input voltage range is between 7 5 and 32 VDC Configuration J5 PIN 1 positive input J5 PIN2 negative input J3 PIN6 Grou...

Страница 5: ...BUS or digital input J3 2 If the input is active the nominal speed is 1800 rpm if the input is inactive the nominal speed is 1500 rpm Switch SWD is a 4 way switch and sets the properties of the availa...

Страница 6: ...ates an order of magnitude for the output value LED flashing slowly 50 on and 50 off minimum output value As the output value increases so does the frequency of the flashing 50 on and 50 off Led on wi...

Страница 7: ...e at a fixed value The value range can be adjusted observing the relative position of the trimmers the limits minimum and maximum are directly proportional to the angles of rotation of the respective...

Страница 8: ...main lit in this mode In this mode SWE dip switches 5 to 8 are no longer read and a CanBus interface will be disabled Using digital input UP PIN 5 of J5 you can select which digital input will be used...

Страница 9: ...you may have an RS485 communication interface or CANBUS interface isolated from the I O and internal logic circuits this results in high immunity to transient voltages and eliminates problems caused...

Страница 10: ...DO NOT USE pin 1 of J4 GND RESERVED A 120 ohm termination resistance should be connected directly to terminals 4 and 2 of J4 On the DIPOT board there is a dip switch selector that can be used to impl...

Страница 11: ...30006 TR2 trimmer TR103 RESET 0 3FF Read value set on trimmer RESET 10bit 30007 30007 Trimmer TR1 TR102 RAMP 0 3FF Read value set on trimmer Ramp 10bit 30008 30008 INPUT 0 5V 0 1023 10 bit Read value...

Страница 12: ...egister the result of the test is 0 not performed 1 OK 2 Error 30026 30026 Minimum value of 0 5V input in points per voltage isolator 30027 30027 Maximum value of 0 5V input in points per voltage isol...

Страница 13: ...0213 TEST CANBUS received messages counter 30221 30221 RPM value received via CAN BUS RPM x 8 E g 1200 8 1500 RPM 30222 30222 RPM GAP received via CAN BUS If 1500 rpm GAP 120 x 8 960 30223 30223 RPM G...

Страница 14: ...CANBUS line with our boards DST4400 DST4601 DST4601PX GC310 GC350 and GC500 The CANbus interface should not be powered from an outside source as it powered by a DC DC source in the device Connect the...

Страница 15: ...utput current This switch depends on the type of speed regulator used DIP 7 REMOTE LOCAL CONTROL it should be ON so the current loop output value is determined by the CANBUS command DIP 8 Rpm1500 1800...

Страница 16: ...16 User s Manual DIPOT MODULE...

Страница 17: ...the right to modify this document without prior notice SICES has made any effort to ensure that the information herein provide are correct in any case SICES does not assume any liability for the use t...

Отзывы: