D-PRO Protection relay Technical Manual 11
4.4
The D-PRO protection relay is equipped with four relay outputs with dry contact in exchange,
max.
10A/250Vac
all fully adjustable.
Terminal
Type
Function
Output
Function
configured
JL - 1
Relay,
10A
250Vac
N.O.
Output 01
DOF.0000 - Not
used.
JL - 2
N.C.
JL - 3
COM.
JL - 4
Relay,
10A
250Vac
N.O.
Output 02
DOF.0000 - Not
used.
JL - 5
N.C.
JL - 6
COM.
Terminal
Type
Function
Output
Function
configured
JI - 1
Relay,
10A
250Vac
N.O.
Output 03
DOF.0000 - Not
used.
JI - 2
N.C.
JI - 3
COM.
JI - 4
Relay,
10A
250Vac
N.O.
Output 04
DOF.0000 - Not
used.
JI - 5
N.C.
JI - 6
COM.
4.4.1
All controller digital outputs (JL and JI) are fully adjustable individually. Each output is
associated to the following parameters:
•
A parameter that configures the function (P.3001 for the input 1):
•
A parameter that configures the output activation mode (P.3002 for the input 1):
o
0-Normal: the output manages the command guaranteeing a minimum activation
time (if the time set is different from zero).
o
1-Maintained: the output stays active up to the reset command.
o
2-Impulsive: the output activates for the time set and stays deactivated until a
new command change.
•
A parameter that configures the impulse activation or duration minimum time (P.3003 for
the input 1). By setting it to zero, the output command stays stable on ON/OFF.
Parameter
Output
Description
P.3001
Output 1 (JL-1)
Output 01 function.
P.3002
Output 01 type (activation mode).