33
Use and Maintenance Manual ATS LOGICA CONTROL PANEL with ATS115
The approval for the activation of the Source A, as per the Source B, is made by the option
KA
-
RA
and the terminals
101-102-110
-
111
to add to the terminal board
XM
. Connect the option as
indicated by the scheme.
WARNING:
When connected to the relay KA, connect the wire 2.12A to the terminal 12/24 of
RA according to the battery voltage.
To manage the Source A as Genset you must configure the following parameters:
P.0100 = 1
P.0113 = 0.0
P.0115 = 60.0
P.0118 = 999.0
P.0304 = 0-No
P.2001 = 4004
P.2002 = 1.0
P.2003 = Source A stop
P.3005 = 1001
This controller is equipped with communication ports for the connection to PC, Modem, Networks,
etc. (see also the ATS115Plus manual)
The controller is designed to acquire an input that inhibit the operation in case of lack of sources
voltage. Accomplish the option wiring as reported in the diagram adding the terminals
105-106
to
the terminal board
XM
.
Configure the parameter:
P.0213 = 2501