background image

REMOVE

FORCE

 Always cut CO

2

 

and outlet tubing at least 2 ft. 

[.6 

M

]

 longer to provide a "service loop" so the B-I-B rack 

can be moved for cleaning or service.  

 Use new (clean), 

1

/

4

I.D. 

[6mm],

 flexible, high pressure, braided tubing from the CO

2

 / air regulator to 

the pump.  

 

NOTE:

 N

EVER

 connect a transfer tank "system" in series with a B-I-B system.  Syrup contaminants in old 

components may work their way through the air supply causing premature failure of the gas 
pump.  The gas used to drive the pump 

M

UST

 be clean and contain no contaminants 

(syrup, oil, 

rust, water,

 

etc)

.  Air compressors may be used with proper particle filters and moisture 

separators.  Air storage tanks should be drained regularly.  Pumps subjected to contaminated air 
are not covered by warranty. 

WARNING: 

High concentrations of CO

2

 

can be fatal as it will displace the air from non-ventilated areas.  

Pumps operated by CO

2

 must be in ventilated areas.  If placed in a confined area 

(basement, 

closet, cooler box, etc.)

, exhaust fans capable of changing the room air on a continuous basis 

should be used.  

 All tubing connections must be secured with stainless steel, stepless Oetiker

®

 clamps.   

 Cable-tie all tubing securely to prevent kinks or sags that inhibit performance or cause damage to the 

pump fittings. 

START-UP PROCEDURE

 

1.

 Confirm that all tubing connections are properly clamped, fittings are tight, and tubing is not kinked.  

Install bag connector to the B-I-B. 

2.

 Adjust gas regulator to

 

 about 20 psi. 

[1.4 bar]

 allowing the pump to stroke slowly. 

3.

 Operate the valve until all air trapped within the tubing has been purged. 

4.

 Once the air has been purged, adjust the CO

regulator to the pressure necessary to maintain the 

desired brix.  The most efficient gas usage occurs at 40 psi. 

[2.8 bar]

.  

M

AXIMUM

 static gas pressure to 

the pump is 85 psi. 

[5.8 bar]

, minimum 20 psi.

 [1.4 bar]

CAUTION:

 Flowrates that result in a stroke-rate of more than two strokes per second will decrease pump life. 

(Consult factory)

  Pump failure due to "overrunning" is not covered by the limited warranty.    

NOTE:

 

To prevent air from entering the system always leave the bag connector attached to the empty B-I-B 
until a new B-I-B can be installed.  Air entered into the system, via air in the bags or vacuum leaks, 
may cause brix fluctuation, foaming, spitting, non-operation of the vacuum sold-out or pump "run-on"  
with the valve closed.  Symptoms of this kind can lead to a misdiagnosis of the pump. 

MOUNTING CLIP KNOCKOUT REMOVAL

 

Removal of the knockout tabs from the pump housing is only necessary if the pump will be installed onto 
a SHURflo Mounting Board.  Depending on board style, spring clip orientation varies.  Ensure spring clip 
position and corresponding knockout tabs before removal.

 

NOTE:

 

The knockout tabs 

must not

 be pushed into the housing cavity.  Failure to 

remove the tab from the housing will cause the spring clips not to engage 
completely, making the mounting insecure.

 

1. 

Position the pump on its side, in a

 secure

 location where the pump can be held 

firmly. 

2. 

Place an appropriate sized flat blade screwdriver into the indentation as shown. 

NOTE:

 Breaking the tabs at this particular indentation facilitates complete tab removal. 

3. 

Break the tabs loose by either pressing firmly, or striking the screwdriver handle solidly with 
your palm. 

4. 

The tab should break away from the housing, allowing it to be popped-out with the screwdriver. 

Removal of the aluminum mounting bracket may be required to permit full engagement of the spring clips.  Screw torque 
15-18 in/Lb. [17-20 N•m]  

Содержание HeavyDuty Advantage BIB 94-360-00

Страница 1: ...uality drink at the dispenser head The above design configuration results in the greatest efficiency and lowest pressure drop every time the dispensing valve open and closes and thus insuring consiste...

Страница 2: ...97 mm Size FLOport 6 0 H x 5 9 W x 4 3 D 152 mm x 150 mm x 110 mm Displacement 3 4 oz 74 cc cycle Suction Lift Activated 20 in Hg 508 m bar wet 25 in Hg 847 m bar Maximum Operating Pressure 85 psi 5...

Страница 3: ...e compressed gas drives the pump and does not come in contact with the syrup The minimum gas pressure is 20 psi 1 4 bar and the maximum is 85 psi 5 8 bar The figures below illustrate the flow of gas a...

Страница 4: ...At equalization the pump stops Sold Out The pump operates only when there is an adequate supply of syrup Vacuum produced by the pump evacuates the syrup within the bag Once the preset vacuum point is...

Страница 5: ...d purging of the liquid outlet lines when the BIB is empty The Shurflo BIB pump ensures drink quality from the first drink to the last The SHURflo pump is compatible with all types of dispensing equip...

Страница 6: ...s Nitrogen or Clean Compressed Air Materials of Construction Polypropylene EPDM Santoprene 316 Stainless Steel Temperature Limits 34 120 F 1 1 49 C Weight 2 lbs 0 9 kg Size 7 9 H x 5 7 W x 3 8 D 171 m...

Страница 7: ...l Specifications Design Two Chamber Double Diaphragm Power Source CO2 gas Nitrogen or Clean Compressed Air Materials of Construction Polypropylene EPDM Santoprene 316 Stainless Steel Temperature Limit...

Страница 8: ...bow 3 8 plastic barb elbow 1 4 plastic barb Tee w check valve none yes 94 366 51 Blue High Altitude H D A syrup pump 3 8 SS barb elbow 3 8 plastic barb elbow 1 4 plastic barb elbow w check valve none...

Страница 9: ...poppet seals causing the pump to fail The cooler temperature causes the viscosity of the product to increase making the pump to work harder to move the same amount of syrup In ventilated areas only h...

Страница 10: ...meters longer than required to provide a service loop This allows the BIB rack to be moved for cleaning or service 5 Oetiker clamps All tubing connections must be secured with stainless steel stepless...

Страница 11: ...Maximum static gas pressure to the pump is 5 8 bar 85 psi minimum is 1 4 bar 20 psi Any time the pressure is changed on the BIB system the brix should be checked to ensure drink quality Notes Flow ra...

Страница 12: ...ates but will not prime dispenser valve open Consult Start up Procedure for proper priming Pump valves have no moisture dry Add water to the inlet port with pump stroking slowly Vacuum leaks at Q D ba...

Страница 13: ...specified To calculate the losses in the system in feet obtained the maximum horizontal tubing length in feet and multiply by 1 instead of 3 Example 1 The tables indicate that heavy soda syrup with 15...

Страница 14: ...Feet Meter Feet Meter 0 5 15 500 152 500 152 500 152 0 75 22 5 500 152 500 152 500 152 1 0 30 453 138 500 152 500 152 1 5 45 212 65 500 152 500 152 2 0 60 102 31 500 152 500 152 2 5 75 64 19 398 121...

Страница 15: ...Beverage Gas Pump ensures quality from the first drink to the last APPLICATION INFORMATION Beverage Gas Pumps are intended for soda syrups and low viscosity concentrates that do not contain solids The...

Страница 16: ...under vacuum SHURflo can recommend several other methods to meet the requirements for a particular installation including Pressurized Inlet Pumps or Accumulators Contact SHURflo for more information I...

Страница 17: ...to the pressure necessary to maintain the desired brix The most efficient gas usage occurs at 40 psi 2 8 bar MAXIMUM static gas pressure to the pump is 85 psi 5 8 bar minimum 20 psi 1 4 bar CAUTION F...

Страница 18: ...of time should be sanitized prior to being placed back in service CAUTION Never apply pressure to the pump s liquid i nlet Pressurized tanks may damage internal components if used to sanitize or purg...

Страница 19: ...s at Q D barb fitting clamps or inlet fitting o ring Excessive amount of air in B I B from improper packaging Air trapped in outlet tubing and or fluid chambers AIR IN INLET AND OR OUTLET TUBING Vacuu...

Страница 20: ...all SHURflo be liable for any indirect incidental or consequential damages of any kind incurred by the reason of the use or sale of any defective product or part This limited warranty covers beverage...

Страница 21: ...once vacuum above 20 in Hg 508 mm Hg is obtained When a new B I B is connected the vacuum drops the pump automatically resumes pumping PUMPING CAPABILITY Due to diversity of both the installations and...

Страница 22: ...22 2 77 23 153 47 Tomato 1 5 1 1 0 29 6 56 17 105 32 1 25 37 0 29 9 50 15 1 5 44 4 13 4 27 8 500 1000 cP FLOW RATE 3 8 10mm I D TUBING 1 2 13mm I D TUBING O J Natural 3 1 0Z SEC CC SEC FEET METER FEE...

Страница 23: ...ants syrup oil rust water etc Air compressors may be used with proper particle filters and moisture separators Air storage tanks should be drained weekly Pumps subjected to contaminated air are not co...

Страница 24: ...concentrate residue Turn OFF CO2 pressure to the pump 3 Prepare 1 gallon 3 8 L of detergent solution in a clean container Mix at the ratio of 1 oz 30 cc of detergent per each gallon of warm water a Pl...

Страница 25: ...date of manufacture The limited warranty will not apply to pumps that were improperly installed misapplied or not suitable with components of other manufactures The limited warranty will not apply to...

Страница 26: ...ired Activated at 20 in Hg 508 mm Hg 34 120 F 1 1 49 C 2 lbs 9 kg Standard plastic 1 4 6mm 90 Optional T or 90 plastic or brass All with internal check valve 3 8 13mm Barb Plastic 90 black Polypropyle...

Страница 27: ...PABILITY Variables within individual systems can affect total pumping distance A gas pumps ability to deliver condiment is limited by the physical demands of the dispensing system Prior to installing...

Страница 28: ...of 10 ft 3M with NO MORE than a 5 ft 1 5M vertical rise Tie wrap all tubing securely to prevent kinks or sags that inhibit performance or cause damage to the pump fittings Use new 1 4 6mm high pressur...

Страница 29: ...25 included with this manual will assure compliance with NSF listed sanitizing requirements for the SHURflo Particulate pump only Consult other equipment manufacturer s instructions for their sanitizi...

Страница 30: ...d to the repair or replacement of the product Warranty replacements will be shipped on a freight allowed basis SHURflo reserves the right to choose the method of transportation Pumps found not defecti...

Страница 31: ...0630 800 854 3218 562 795 5200 FAX 562 795 7564 Shipping 5900 Katella Ave Suite B Cypress CA 90630 SHURflo East 52748 Park Six Court Elkhart IN 46514 5427 800 762 8094 219 262 0478 FAX 219 264 2169 19...

Страница 32: ...ke slowly Once the pump is primed the regulator can be adjusted up 4 Continue dispensing syrup until all the air trapped within the tubing has been purged 5 Once the air has been purged adjust the CO2...

Отзывы: