background image

 

BLASTER

 

SERIES WASH-

DOWN PUMP

 

SHURflo's Blaster series pumps are designed to handle the harsh 
marine environment.  Blaster motors have 

precision ball bearings

 

supporting the armature.  Each motor is protected by an integral

 thermal 

breaker

, and are all 

U/L Marine listed

.  Blaster pressure 

switches are 

sealed

 and the motors are finished with a baked-on 

polyurethane 

coating

 to inhibit corrosion.  The "Pro-Blaster" motor is sealed in an 

exceptionally tough 

epoxy powder coated finish

, allowing it to be in 

environments where "splashed water" may be present.  Blaster series 
pumps are enclosed to prevent incidental moisture from entering; 
however, they 

are not submersible

 units. 

 
The Blaster delivers water on demand. With the spray nozzle off 

(output 

side closed)

 the pump will turn off.  As the nozzle is opened the pressure 

within the hose 

(output side)

 drops.  Once the pressure drops below a 

predetermined point the pumps pressure switch closes and the pump 
operates. With the nozzle set at a fine mist the pump will cycle, as it is 
able to pressurize the hose faster than water being released. If the spray 
nozzle is held wide open the pump will operate continually.  The pump 
may momentarily operate even after the nozzle is closed, as it 
pressurizes the hose. Once the pressure setting is reached the switch 
opens and the pump stops. 

DUTY CYCLE

 

Wash-down pumps are rated for intermittent duty (only), as they operate at higher than average pressures.  Operating a pump continuously for more 
than twenty (20) minutes, within an hour period, is not recommended.  Actual duty cycle is determined by amp draw, temperature, and rate of cycling.  

NOTE:

  Rapid cycling should be minimized to ensure long life.  Rapid cycling is defined as

 ON

/

OFF

 within two seconds. 

911-444  Rev. E     10/98 

 
 
 

MOUNTING 

 

• 

Consider a

 dry

 location that allows easy access 

if maintenance is required.  The pump should 
not be located in an area of less than one cubic 
foot unless adequate ventilation is provided. 
Excessive heat may trigger the integral thermal 
breaker and interrupt operation. When the 
temperature drops the breaker will automatically 
reset and start operation. 

• 

Mount higher than the outside water (sea) 
level. The pump is capable of a 6 ft. [2

M

vertical prime above the outside water level. 
The pump can be mounted in any position.  If 
mounting the pump vertically, the pump head 
should be in the down position. 

CAUTION:  Do not

 drive screws through the 

vessel's hull. 

 

• 

Use 

#

8 stainless steel hardware to fasten the 

pump. Choose a 

solid

 surface

 (bulkhead or 

stringer)

 that will not amplify pump sound. The 

mounting feet are intended to isolate the pump 
from the mounting surface; over-tightening, 
flattening, or oversized screws will reduce the 
mounting pads ability to isolate vibration/noise. 

ELECTRICAL

 

• 

The pump should be on a dedicated 

(individual)

 circuit protected on the positive (+ 

red) lead with the proper size "slow blow" 
fuse.  For all 12

VDC

 pumps use a 15 amp 

fuse, on 24

VDC

 pumps use a 10 amp fuse. 

The total current draw on the circuit 

must not

 

exceed 15 amps. 

INSTALLATION AND OPERATION MANUAL 

Отзывы: