- 12 - 

5.1.1

     

Abnormal noise 

 

       

    If an abnormal noise occurs, stop operation immediately and perform inspection. 

Possible types and causes of abnormal noise: 

             

 Bearing noise 

Abnormality or end of service life of motor bearings 

 Contact noise 

Impeller or casing deformation/damage 
Intake of foreign object 
Looseness due to loose bolt 

 Vibration noise 

Please refer to the following section “Vibrations”. 

  Pulsating noise (unsteady flow noise) 

Excessive closing off of flow volume   
Excessive resistance of equipment 

5.1.1

   

Vibrations 

 

If vibrations exceed the acceptable values, stop 
operation and perform inspection. 

 

Reference values for acceptable vibration 

Motor pole count 

(P) - Frequency 

(Hz) 

Rotation 

speed  

(min

-1

Acceptable 

vibration value   

(µm; p-p) 

6 - 50 

Approx. 970 

Approx. 118 

6 - 60 

Approx. 1170 

Approx. 97 

4 - 50 

Approx. 1450 

Approx. 79 

4 - 60 

Approx. 1750 

Approx. 65 

2 - 50 

Approx. 2950 

Approx. 38 

2 - 60 

Approx. 3500 

Approx. 32 

Acceptable value at vibration speed of 6mm/s 

 

Possible causes of vibrations: 

  Unbalance of impeller due to dust adhesion 

  Deformation/damage of impeller or casing 

  Abnormality of motor shaft or bearings 

  Looseness due to loose bolt 

  Stall operation; unsteady flow   

  Transfer or resonance of vibrations from ducts or base 

  Insufficient rigidity of ducts or base 

5.2

 

Stopping operation and restarting after stopping 

When operation will be stopped, consideration should be given to the storage conditions even if the stopped 
period will be short. To prevent rusting of the bearings, etc. during the stopped period, turn the impeller by hand 
about 10 times once per month, or run it empty for about 5 minutes once per month. Also, when restarting 
operation, be sure to perform the same inspections as were done for test operation. In particular, be sure that 
nothing is adhered to the impeller and check that there is no corrosion.

Rotation speed (min

-1

Acceptable vibration value diagram

 

Acceptable 

vibration value

 

Acceptable vibration 

value when using 

vibration-damping 

equipment

 

To

ta

l amplitude (µm)

 

Acceptable 

Unacceptable

Rotation speed (min

-1

Acceptable vibration value diagram 

Содержание KAIRYU

Страница 1: ...MAA4060 Y004E Fan Instruction Manual Axial fan with adjustable at rest blades KAIRYU smooth flow Instruction manual for motor direct drive type...

Страница 2: ...rence Applicable types for this instruction manual This manual provides instructions on how to set up and use the following fan types Fan type KAIRYU series Axial fan with adjustable at rest blades Fa...

Страница 3: ...pon receipt and product verification 8 3 2 Movement transportation 8 3 3 Storage until installation 8 4 Installation 8 4 1 Mounting 8 4 2 Connection to ducts 9 4 3 Electrical wiring 10 4 4 Test operat...

Страница 4: ...e of this do not place your face close to the outlet When hanging be sure to use the holes labeled Hang here Hanging by other parts may result in deformation of the fan or cause an accident by tipping...

Страница 5: ...If this occurs avoid operation at those frequencies Shipment inspection of the fan is performed only at the rated rotation speed Operation at other speeds frequencies is not guaranteed Operation testi...

Страница 6: ...acceleration time is short an over current error may occur Deceleration time 30 to 60 sec or more If the decceleration time is short a regenerative current error may occur 3 Other precautions Vibratio...

Страница 7: ...formance number Blade angle number Voltage V Frequency Hz Indication types contents A Axial fan 1 Low noise type low speed specifications D Motor direct drive type 3 300 A 0 4 1 Large Air volume Small...

Страница 8: ...A or AC4C 5 Impeller hub FC200 6 Casing SS400 SPHC 7 Motor 8 Terminal box When using a flange mounted motor When using a foot mounted motor Note The diagram is an example and shows typical part shapes...

Страница 9: ...for lifting For safety the fan should be lifted by at least 2 labeled hangers except for products with only 1 hanger Lifting should be performed by licensed personnel only 3 3 Storage until installati...

Страница 10: ...ition vertical mounting of fans with foot mounted motors is not correct If the fan will be mounted in a high location and especially frequent inspection or repairs are expected lifting equipment shoul...

Страница 11: ...er to the motor instruction manual Be sure to wire the fan properly so that the rotation direction is correct For details refer to section 4 4 4 4 Test operation Before performing test operation be su...

Страница 12: ...are recorded abnormalities can be detected early to prevent problems 1 Check for vibration or abnormal sound once every three months and inspect the insulation once a year Inspect the motor while ref...

Страница 13: ...of 6mm s Possible causes of vibrations Unbalance of impeller due to dust adhesion Deformation damage of impeller or casing Abnormality of motor shaft or bearings Looseness due to loose bolt Stall oper...

Страница 14: ...actors such as salt damage and public pollution abnormal voltage use of a power supply voltage or frequency other than that specified or the like Failure or damage due to repair or modification includ...

Страница 15: ...of oil Replacement or recycling Inappropriate material Replacement Unbalanced impeller Correction Deformation or damage of impeller Repair or replacement Wear or corrosion of impeller Repair or repla...

Страница 16: ...n information that you may need when making an inquiry of us Model Serial No Purchased on Date Starting day Date Distribution agent TEL In charge SHOWA DENKI CO LTD 1 25 Shinden Kita machi Daito City...

Отзывы: