Select cable for use that has sufficient thickness and an allowable current for use, and
distance from the generator to the equipment using the generator.
< Note >
Select cable with thickness that ensures the voltage drop across the cable would be
within 5% of the rated voltage.
Load Cable Selection Tables
(Ex.) If used voltage is 120 V and voltage drops by 6 V.
Single-phase Cabtyre cables
(Unit: AWG)
Length
200 ft. (61 m)
or less
300 ft. (91 m)
400 ft. (122 m)
Current
10 A
10
8
8
20 A
8
6
4
30 A
6
4
2
50 A
4
2
1/0
7-2. Connecting Load Cables
WARNING : ELECTRIC SHOCK
Always turn all the breakers OFF, place the starter switch in the STOP
position and stop the engine before attaching / detaching the load cable to the
output receptacle.
Do not insert a pin, needle or other metal object into the receptacle.
Do not touch the generator if the generator or casing becomes wet during
operation.
CAUTION : FIRE
Do not connect the generator output to indoor wiring.
< Note >
When connecting a load, check that the generator output setting, output receptacle connection
position, and load power source are all matching.