Shindaiwa DG25MK Скачать руководство пользователя страница 31

 

28 

Set frequency. (Refer to section"

5-4. Frequency change

" ) 

Turn the Circuit Breaker to OFF position. 
Turn the Power Switch to ON position. 

 

< Note > 

 When turn the Power Switch 

to the ON position, the “Low Oil Pressure” and “High Coolant 

Temperature” warning indicators will illuminate, but all indicator lights will turn off when the 
engine is started. 

 

Press the Manual Mode Button. 
Press the Start Button to start the engine. 
Adjust voltage using the voltage regulator dial. 

 

50Hz Operation 

400V [200V] 

60Hz Operation 

440V [220V] 

* The values in brackets are for when set to 200/220V. 

 

Press the Stop Mode Button to shut off the engine.   
Press the Auto Mode Button. 
Turn the Circuit Breaker to ON position. 
The engine starts when the RS1/RS2 terminals close. 

 

<

 Note > 

 Please keep in mind that the muffler may emit some smoke when engine is started. 

 The battery is always drained while Auto Mode is selected. Start the engine at least once a 

week to charge the battery. 

9-2.  Procedures during Operation 

(1)  Checks after Startup 

 Make sure that the controller and hour meter 

are in normal status. (Refer to section “

5. 

Equipment

”.) 

 Check that there is no abnormal vibration or noise. 

 Check that the exhaust gas color is normal. When operation is normal, the exhaust gas should 

be colorless or slightly bluish. 

< Note > 

 If abnormal, stop using this generator and request authorized distributor where the generator 

was purchased to repair the generator. 

(2)  Adjustment during Operation 

During load operation, check the voltage on the Operation Display and finely adjust 
voltage using the voltage regulator dial. 

 

 

Restarting after stopping due to running out of fuel. 

The fuel filter includes an automatic air-bleeding device. Restart the engine according 
to the following procedures even if the engine has stopped due to running out of fuel. 

 

Add fuel to the generator. 
Press and hold the Lamp Test / Air Bleeding Button for approximately 2 seconds to 

automatically starts air-bleeding device. 

A

ir-bleeding device runs for up to 4 minutes. 

Press the Manual Mode Button. 
Press the Start Button, and confirm the engine has started properly. 

< Note > 

 Start the engine and check that the air is completely bled from the system. If air bleeding is not 

complete, engine rotation will not be stable. In that case, repeat the air bleeding operation. 

10 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Содержание DG25MK

Страница 1: ...rtical Water Cooled 4 Cycle Diesel Engine DG25MK 400M R X753 007 95 1 X753801 350 1 CAUTION Do not operate the Generator or any other appliance before you have read and understood the instructions for...

Страница 2: ......

Страница 3: ...ration Store this manual in a specified location where it will be secure and available for consulting at any time Order another copy from the authorized distributor where this generator was purchased...

Страница 4: ...18 7 Load Connections 19 7 1 Load Cable Selection 19 7 2 Connecting Load Cables 19 7 3 Earth Leakage Relay and Grounding 21 8 Pre Operation Inspection 22 8 1 Checking Engine Oil 22 8 2 Checking Coolan...

Страница 5: ...rocuted by short circuit Be sure to test generator s insulation resistance periodically Grounding should be made after the engine is stopped Whenever the Earth leakage relay is activated you should al...

Страница 6: ...unding components immediately after stopping the engine as they are still extremely hot Do not open the radiator cap immediately after stopping the engine to avoid sustaining burns from hot vapor Hot...

Страница 7: ...etting output terminal connection and load power source are consistent Cable burnout can occur due to generated heat if the load current exceeds the allowable current of the cable The voltage drop bet...

Страница 8: ...ed locations Order labels using part number indicated in the parenthesis Injury Part no X505 007550 Electric shock Part no X505 007560 Caution gm spec LLC Part no X505 007840 Caution fire Part no X505...

Страница 9: ...d speed min 1 1500 1800 Displacement L 2 434 Combustion system Direct Fuel Injection Cooling method Radiator Lubricating method Forced lubrication Starting method Electric start Fuel Diesel Fuel ASTM...

Страница 10: ...15 to 40 C Relative humidity 85 or less Elevation 300 m or less Power source for submerged pumps and similar civil engineering equipment Power source for lighting and similar equipment Power source fo...

Страница 11: ...uel Return External Tank Fuel Inlet Water Separator Battery Alternator Check Door 3way Fuel Valve Air Cleaner Coolant Drain Plug Oil Drain Plug Fuel Filter Oil Filler Accessories Owners Manual Door Ke...

Страница 12: ...9 Inside 4 2 Operation Panel Part Names Circuit Breaker Controller Power Switch Hour Meter Voltage Regulator Earth Leakage Relay Frequency Selector Switch inside...

Страница 13: ...rms Manual Mode Button This button places the controller into its Manual Mode Refer to section 9 1 Initial Startup Pre Check 1 Manual Start Auto Mode Button This button places the controller into its...

Страница 14: ...ar To exit sleep mode press any button on the controller Main screens Status Status Screen Contents Generator at Rest Engine is stopped Generator Available Engine is running Generator Locked Out It is...

Страница 15: ...se Sequence No use Active Config Ph N voltage frequency voltage set in the Alt Config is displayed Mains Status Screen Contents Mains Voltage No use Mains Frequency No use Mains Phase Sequence No use...

Страница 16: ...Power Switch is in the ON position It will cause injury by rotating parts such as cooling fans and fan belt Always turn the Power Switch to the OFF position and stop the engine then close and lock OP...

Страница 17: ...it is insufficient Refer to section 8 2 Checking Coolant If the coolant is at the specified amount it is probable that the fan belt is loose or there is a coolant leak Wait for the engine to cool and...

Страница 18: ...el Low If the amount of fuel is small Fuel Level Low appear on the Operation Display and the engine will be automatically stopped Check if there is a sufficient amount of fuel and add fuel insufficien...

Страница 19: ...OPERTY DAMAGE When changing the frequency be sure to change both the Frequency Selector Switch and Controller settings Loosen the two screws to open the operation panel Change the Frequency Selector S...

Страница 20: ...ernal fuel tank to the external fuel inlet and the external fuel return Change the lever of the 3way fuel valve to the B side to supply fuel from the external tank Refer to 9 5 Connecting an External...

Страница 21: ...nerator set up barriers or fencing completely around the boundary line of the construction area and take measures to prevent persons not involved in the construction from entering the area Position th...

Страница 22: ...Tables Ex If used voltage is 440V and voltage drops by 22 V 3 phase Cabtyre cables Unit AWG Length 30 m or less 61 m 91 m 122 m 152 m 183 m Current 20 A 12 12 12 12 12 12 25 A 12 12 12 12 12 10 30 A...

Страница 23: ...burnout 1 3 Phase Output Terminal For 3 phase load Terminal voltage is 400 440 V 200 220 V 50 60Hz The values in brackets are for when set to 200 220V For 1 phase load Terminal voltage is 230 254 V 1...

Страница 24: ...ctrician should perform the grounding of the following 3 points 500 or below The Bonnet grounding terminal of the generator The Earth leakage terminal of the generator The Bonnet of the load Note In t...

Страница 25: ...OPERATION PANEL DOOR before checking or maintaining the engine or any equipment Do not open the check door when the Power Switch is in the ON position It will cause injury by rotating parts such as co...

Страница 26: ...tank with coolant until it reaches the FULL line Re attach the cap 2 Filling the Radiator Remove the radiator plate Remove the radiator cap Fill with coolant through the filler neck until the radiato...

Страница 27: ...hecking the Fuel CAUTION FIRE This generator uses diesel fuel Always be sure to stop the engine and not bring flames close when inspecting fuel or refueling Wait until the engine has cooled before per...

Страница 28: ...uid level and add distilled water until it reaches the upper level when the fluid level is near the lower level Check the terminals for looseness and tighten properly Note It is necessary to recharge...

Страница 29: ...emperature or humidity or an area with a large amount of dust Do not open any doors during operation Operating with door open can negatively affect cooling effect resulting in an equipment malfunction...

Страница 30: ...perature not less than 30 degrees Pre heating time depends on the coolant temperature Automatically repeats Crank Attempt and Crank Rest up to 3 times Please keep in mind that the muffler may emit som...

Страница 31: ...al status Refer to section 5 Equipment Check that there is no abnormal vibration or noise Check that the exhaust gas color is normal When operation is normal the exhaust gas should be colorless or sli...

Страница 32: ...for a prolonged period If you leave the Power Switch in the OFF position the standby current may drain the battery 9 4 Protective Functions WARNING INJURY Do not open the check door when the Power Swi...

Страница 33: ...efault 115 C 3 Air Filter Clogging The element is clogged making it necessary to clean or replace the element 4 Overload Activates in overload Flashes when at approx 80 of rated output Load rejection...

Страница 34: ...hose with an internal diameter of 8 to 9 mm Set the fuel level of the external fuel tank from 0 to 3 m from the underside of this generator The fuel level of the external fuel tank being lower than th...

Страница 35: ...e enough to prevent the fluid from spilling on the ground Dispose of oil fuel coolant LLC filter battery and other hazardous materials according to laws and regulations concerning industrial waste Con...

Страница 36: ...arator and Gauze filter Clean Fuel tank Clean Check for leaks Fuel Oil Coolant Fuel Cooling Water Oil Hoses and Anti Vibration Rubber Replace Every 2 years Air cleaner element Clean 1st time at 50hrs...

Страница 37: ...ain plug and shortly after starting the engine be sure to always check that there is no oil leakage 2 Replacing the Oil Filter First Time 50 hours Thereafter Every 200 hours Drain the engine oil Refer...

Страница 38: ...except cleaning Element part no 1401 42271 Kubota part no Cleaning the air filter element If dry dust is adhering Blow compressed air from inside the element If carbon or oil is adhering Replace with...

Страница 39: ...rain Water Every 200 hours Remove the fuel drain plug and packing with rubber seal After the water has been drained reinsert the fuel drain plug with new packing with rubber seal Note Replace the pack...

Страница 40: ...by extensive light load WARNING EXHAUST GAS POISONING Do not operate the generator in poorly ventilated areas such as an indoors or tunnels as the exhaust gas of the engine contains substances that ar...

Страница 41: ...age Procedures Perform the following maintenance procedures before storing this generator if it is not going to be used for two months or more Remove the battery Refer to section 8 7 Checking the Batt...

Страница 42: ...tor when it is double stacked WARNING ELECTRIC SHOCK INJURY Do not touch output terminals or internal electric parts while the generator is operating Do not open the check door when the Power Switch i...

Страница 43: ...line is frozen 3 Pre heater is defective 1 Use winterized fuel 2 Drain water in fuel line 3 Ask our distributor to repair Engine starts but stalls immediately 1 Fuel filter is clogged 2 Gauze filter i...

Страница 44: ...tive 2 AVR is defective 3 Improper load cable connection 1 Ask our distributor to repair 2 Ask our distributor to repair 3 Correctly set the connection location to the output terminal The voltage drop...

Страница 45: ...42 1 400 440V 13 Generator Circuit Diagram...

Страница 46: ...43 2 200 220V...

Страница 47: ...44 14 Engine Electrical Circuit Diagram...

Страница 48: ...2019...

Отзывы: