- 7 -
4-4. Table of measuring range code
Measuring range
Input type
Code
°
C
°
F
B
0
~
1800
0
~
3300
R
0
~
1700
0
~
3100
S
0
~
1700
0
~
3100
K
−
199.9
~
800.0
−
300
~
1500
K
0
~
1200
0
~
2200
E
0
~
700
0
~
1300
J
0
~
600
0
~
1100
T
−
199.9
~
300.0
−
300
~
600
N
0
~
1300
0
~
2300
*1
U
−
199.9
~
300.0
−
300
~
600
*1
L
0
~
600
0
~
1100
Thermo-
couple
*2 WRe5-26
0
~
2300
0
~
4200
−
200
~
600
−
300
~
1100
R.T.D.
Pt100
−
100.0
~
100.0
−
150.0
~
200.0
0 ~ 10mV
0 ~ 5V
1 ~ 5V
Voltage
0 ~ 10V
Current
4 ~ 20mA
Initial value: 0.0 ~ 100.0
Scaling range:
−
1999 ~ 9999 count
Span: 10 ~ 5000 count
Thermocouple:
B, R, S, K, E, J, T, N: JIS/IEC
*1 Thermocouple
U, L: DIN43710
*2 Thermocouple
WRe5-26: Hoskins product
R.T.D. Pt100:
New JIS/IEC
Note:
When the measuring range is changed, data related to measuring range,
such as set value and alarm setting value are initialized.
4-5. Table of alarm type code
Alarm code can be assigned each for AL 1 and AL 2 independently.
Alarm
code
Alarm type
Inhibit
action
*1
Communic
ation
Remarks
HL__
No
1
HL_S
Higher
limit
absolute
value
Yes
2
Output ON, also in case of sensor
breakage or higher limit scale-over
LL__
No
3
LL_S
Lower limit
absolute
value
Yes
4
Output ON, also in case of lower
limit scale-over
*1 During communications, Read and Write become possible at the above values.
4-6. Method of shifting screens
(1) Method of shifting between Mode 0 screen group and Mode 1 screen
group
By pressing the
key on the basic screen for 3 seconds or longer,
the display changes to the parameter heading screen of Mode 1
screen group. To return to the basic screen, keep pressing the
key again for 3 seconds or longer.
(2)
Method of shifting screen within Mode 0 screen group
By each pressing of the
key, screen shift takes place.
When the light of decimal point of the lowest digit place is OFF, by each
pressing of
ENT
key, the screen shifts alternately between the parameter
character indicating screen and the parameter setting screen.
(3)
Method of shifting screen within Mode 1 screen group
By each pressing of the
key, screen shift takes place.
When the light of decimal point of the lowest digit place is OFF, by each
pressing of
ENT
key, the screen shifts alternately between the parameter
character indicating screen and the parameter setting screen.
(4)
Method of setting input scaling screen in Mode 1 screen group
On condition that "Lower limit value < Higher limit value", when the lower
limit value is set with a difference less than 10 counts from that of the higher
limit value, the higher limit value is forcibly changed to a new value at lower
limit value plus 10 counts.
As a result, when the higher limit exceeds 9999 counts, it is changed to the
value of the lower limit value minus 10 counts. Also, when a lower limit
value is set at a value with a difference exceeding 5000 counts from the higher
limit value, the higher limit value is forcibly changed to a new value at lower
limit value plus 5000 counts (
−
5000 counts).
On condition that "Lower limit value < Higher limit value", when the higher
limit value is set with a difference less than 10 counts from that of the higher
limit value, the lower limit value is forcibly changed to a new value at higher
limit value minus 10 counts.
As a result, when the lower limit exceeds
−
1999 counts, it is changed to the
value of the higher limit value plus 10 counts. Also, when a higher limit
value is set at a value with a difference exceeding 5000 counts from the lower
limit value, the lower limit value is forcibly changed to a new value at higher
limit value minus 5000 counts (+5000 counts).
On condition that "Lower limit value > Higher limit value", when the lower
limit value is set with a difference less than 10 counts from that of the higher
limit value, the higher limit value is forcibly changed to a new value at lower
limit value minus 10 counts.
As a result, when the higher limit exceeds
−
1999 counts, it is changed to the
value of the lower limit value plus 10 counts. Also, when a lower limit value
is set at a value with a difference exceeding 5000 counts from the higher limit
value, the higher limit value is forcibly changed to a new value at lower limit
value minus 5000 counts (+5000 counts).
On condition that "Lower limit value > Higher limit value", when the higher
limit value is set with a difference less than 10 counts from that of the higher
limit value, the lower limit value is forcibly changed to a new value at higher
limit value plus 10 counts.
As a result, when the lower limit exceeds 9999 counts, it is changed to the
value of the higher limit value minus 10 counts. Also, when the higher limit
value is set at a value with a difference exceeding 5000 counts from the lower
limit value, the lower limit value is forcibly changed to a new value at higher
limit value plus 5000 counts (
−
5000 counts).
(5)
Method of setting analog output scaling screen in Mode 1 screen group
On condition that "Lower limit value < Higher limit value", when the lower
limit value is set at the same value of the higher limit, the higher limit value is
automatically changed to the lower limit value +1 count. As a result, when
the higher limit exceeds the higher limit of the measuring range, it is changed
to the value of lower limit
−
1 count.
On condition that "Lower limit value < Higher limit value", when the higher
limit value is set at the same value of the lower limit, the lower limit value is
automatically changed to the higher limit value
−
1 count. As a result, when
the lower limit exceeds the lower limit of the measuring range, it is changed to
the value of higher limit +1 count.
On condition that "Lower limit value > Higher limit value", when the lower
limit value is set at the same value of the higher limit, the higher limit value is
automatically changed to the lower limit value
−
1 count. As a result, when
the higher limit exceeds the lower limit of the measuring range, it is changed
to the value of lower limit +1 count.
On condition that "Lower limit value > Higher limit value", when the higher
limit value is set at the same value of the lower limit, the lower limit value is
automatically changed to the higher limit value +1 count. As a result, when
the lower limit exceeds the higher limit of the measuring range, it is changed
to the value of higher limit
−
1 count.
5. Supplementary explanation
5-1. Display update cycle (Screen No.1-2)
Setting of PV display update cycle on the basic screen is made.
The setting of value is made every 0.5 second.
5-2. Alarm output action (option)
(1)
Setting of alarm higher limit value
For setting the alarm higher limit value, the alarm hysterisis is set by selecting
the higher limit alarm on the alarm code screen of Mode 1 screen group (when
alarm option is attached).
The higher limit alarm is output when the process value exceeds the alarm
level value. The output goes off when the process value comes down below
the alarm level value minus the alarm hysterisis.
(2)
Setting of alarm lower limit value
For setting the alarm lower limit value, the alarm hysterisis is set by selecting
the lower limit alarm on the alarm code screen of Mode 1 screen group.
The lower limit alarm is output when the process value comes down below the
alarm level value. The output goes off when the process value exceeds the
alarm level value plus hysterisis.
5-3. Analog output action (option)
The analog output is a function that outputs the analog voltage or analog
current corresponding to the process value. They are used for input signal
into a recorder and data accumulation equipment.
Within the measuring range specified by the lower and higher limit value of
the analog output scaling, analog output signal to correspond to the process
value is available.
Scaling output diagram
5-4. Auto-return function
On any screen other than 0-0 basic screen, if no key operation is made for 3 minutes
or longer, the screen shifts to the basic screen (auto-return).
6. Error message
Abnormal input of process value (indicated on the basic screen of Mode 0 screen
group)
This message is indicated when the thermocouple or A of R.T.D. is
burnt out, also when PV value exceeds the higher limit of the
measuring range by about 10%.
When PV value is below the lower limit of the measuring range by
about 10%, by reason such as wrong polarity of input wiring.
When the Pt B (terminal No.7) wire breaks.
When the cold junction (CJ) is abnormal on the higher side in
thermocouple input.
When the cold junction (CJ) is abnormal on the lower side in
thermocouple input.
When the B wire (terminal No.9) breaks, or when plural number of
wires out of A
·
B
·
B break.
Note:
When abnormality occurs, please contact our sales agent or to our business
office directly.