System parameter group 00
PARAMETER DESCRIPTION 95
5.1.10 Control mode selection
Select the control mode by setting 00-20(P.400).
Parameter
Name
Default
Setting Range
Content
00-20
P.400
Control mode selection
0
0
Speed control
1
Torque control
2
Position control
Control mode selection
If 00-20(P.400) = 0, torque control is off, and inverter runs speed control in closed-loop vector; 00-20(P.400) = 1,
torque control is on, and inverter runs torque control. In torque control, inverter needs to work in closed loop vector
control mode, so a speed measuring encoder must be installed.
The combination of using 00-20(P.400) control mode selection with digital input function : control mode switch
(03-00
(P.83)
= 55/63) is shown as the following sheet.
00-20(P.400)
Digital input function
Control mode
speed/torque switch (03-00(P.83) = 55)
position/speed switch (03-00(P.83) = 63)
0
Terminal function not set
Terminal function not set
Speed control
1
Terminal function not set
Terminal function not set
Torque control
2
Terminal function not set
Terminal function not set
Position control
0
Terminal function set and signal given
---
Torque control
0
Terminal function set and signal not given
---
Speed control
2
---
Terminal function set and signal given
Position control
2
---
Terminal function set and signal not given
Speed control
5.1.11 Motor control mode selection
Choose control mode for the AC motor.
Parameter
Name
Default
Setting Range
Content
00-21
P.300
Motor control mode
selection
0
0
Induction motor V/F control
1
Induction motor closed-loop V/F control (VF + PG)
2
Induction motor simple vector control
3
Induction motor sensorless vector control
4
Induction motor PG vector control
5
Synchronous motor PG vector control
6
Synchronous motor vector control without PG
00-22
P.370
Second motor control
mode selection
99999
0
Induction motor V/F control
1
Induction motor close-loop V/F control (VF+PG)
2
Induction motor simple vector control
3
Induction motor sensorless vector control
4
Induction motor PG vector control
5
Synchronous motor PG vector control
6
Synchronous motor vector control without PG
99999
Off
Setting
Содержание SA3 Series
Страница 2: ......
Страница 420: ...Appendix 6 European Specification Compatibility Description APPENDIX 418 ...