Protection parameter group 06
PARAMETER DESCRIPTION 196
5.7.19 Output power calculation
Parameter
Name
Default
Setting range
Content
06-31
P.298
Output
power
(lower 16 bits)
Read
only
Read only
There are two decimals, read only and can be written to 0
06-32
P.299
Output
power
(higher 16 bits)
Read
only
Read only
Read only and can be written to 0
Output power value=06-32(P.299)*2
16
+06-31(P.298), and unit is KWH.
5.7.20 Alarm query function
This function provides users with information about latest 12 alarm codes.
Parameter
Name
Default Setting Range
Content
06-40
P.288
Alarm record code
query
1
0~12
06-40 (P.288)value 1~12 corresponds to 06-41(P.289)’s
alarm E1~E12.
06-41
P.289
Alarm record code
display
Read
only
Read only
06-42
P.290
Alarm record message
query
0
0~10
Alarm
message
of No.
06-40
(P.288)
06-42 (P.290) =1, 06-43 (P.291) displays
frequency when 06-40 (P.288) alarm.
06-42 (P.290) =2, 06-43 (P.291) displays
current when 06-40 (P.288) alarm.
06-42 (P.290) =3, 06-43 (P.291) displays
output voltage when 06-40 (P.288) alarm.
06-42 (P.290) =4, 06-43 (P.291) displays
temperature rising accumulation rate when
06-40 (P.288) alarm.
06-42 (P.290) =5, 06-43 (P.291) displays PN
voltage when 06-40 (P.288) alarm.
06-42 (P.290) =6, 06-43 (P.291) displays total
inverter operation time when 06-40 (P.288)
alarm.
06-42 (P.290) =7, 06-43 (P.291) displays
inverter operation status code when 06-40
(P.288) alarm.
06-42 (P.290) =8, 06-43 (P.291) displays
dates (years and months) when 06-40 (P.288)
alarm.
06-42 (P.290) =9, 06-43 (P.291) displays
dates (days and hours) when 06-40 (P.288)
alarm.
06-42 (P.290) =10, 06-43 (P.291) displays
dates (minutes and seconds) when 06-40
(P.288) alarm.
06-43
P.291
Alarm record message
display
Read
only
Read only