Analog input and output parameter group 02
PARAMETER DESCRIPTION 130
5.3.6 Terminal 4-5 signal selection and processing
Choose terminal 4-5 signal specifications, frequency compensation function, and signal polarity .etc.
Parameter
Name
Default Setting Range
Content
02-20
P.17
Terminal 4-5 signal
range selection
0
0
Signal sampling range from 4~20mA.
1
Signal sampling range from 0~10V.
2
Signal sampling range from 0~5V.
02-21
P.39
Terminal 4-5 maximum
operation frequency
50.00Hz
1.00~650.00Hz
50Hz system (00-24(P.189)=1)
60.00Hz
60Hz system (00-24(P.189)=0)
02-22
P.528
Terminal 4-5 filter time
30ms
0~2000ms
---
02-23
P.505
Terminal 4-5 current/
voltage signal
bias rate
0.0%
-100.0%~
100.0%
---
02-24
P.184
Terminal 4-5
disconnect selection
0
0
0: Off
1
Inverter decelerates to 0Hz, muti-function digital output
terminal set off alarm
2
Inverter stops immediately, and keypad displays “AEr” alarm
3
Inverter runs continuously according to the frequency
reference before disconnection. Digital output terminal will
set off alarm.
02-25
P.198
Terminal 4-5 minimum
input current/ voltage
4.00mA
0~20.00mA
---
02-26
P.199
Terminal 4-5 maximum
input current/ voltage
20.00mA
0~20.00mA
---
02-27
P.196
Percentage
corresponds to
terminal 4-5 minimum
input current/ voltage
0.0%
-100.0%~
100.0%
(02-01 (P.501)= 2/14/15/16/17)
-400.0%~
400.0%
02-28
P.197
Percentage
corresponds to
terminal 4-5 maximum
input current/ voltage
100.0%
-100.0%~
100.0%
(02-01 (P.501)= 2/14/15/16/17)
-400.0%~
400.0%
Terminal 4-5 selection and processing
Terminal 4-5 signal selection and the maximum operation frequency
Setting