Terminal wire arrangement
INVERTER INTRODUCTION 27
3.7.5 Control circuit
Control terminal name
Terminal type Terminal name
Function instructions
Terminal specifications
Digital signal
input
STF
These are multi-function control terminals, a
total of 4.
Input impedance: 2.4 kΩ
Action current : 3 mA (when 24
VDC)
Maximum frequency: 1kHz
STR
M0
M1
Analog signal
input
10
+10.5±0.5V
Maximum current:10mA
3
0~10V/4~20mA
Input impedance:10kΩ(0-10V)
or 235Ω(4-20mA)
Relay output
A
Multi-function relay output terminals.
A-C is normal open contact, C is common
terminal.
Maximum voltage : 30 VDC or
250 VAC
Maximum current:
Resistor load 5A NO
Inductance load 2A NO
(cosΦ=0.4)
C
Communication
terminal
RJ45
RS-485、optical coupling isolation.
Highest rate:38400bps
Longest distance:500m
DA+
DB-
Common
terminal
SD/5
COM terminal for STF、STR、M0、M1、10、
3.
---
Arrangement of control terminal
Wires connection
For the control circuit wiring, strip off the sheath of a cable, and use it with a blade terminal. For a single wire, strip off
the sheath of the wire and apply directly.
Please insert a blade terminal or a single wire into the terminal for wiring.
(1) Strip off the sheath for the below length. If the length of the sheath peeled is too long, a short circuit may occur
with neighboring wires. If the length is too short, wires might come off.
Wires should be well connected to avoid messiness. In addition, don’t need to solder it.
7mm