51
4.5.2. DO forced output
The output signals could be forced on/off and do not affect the status of servo drive. This function
is used for output signal wiring check, etc. This operation must be performed in the servo off state by
turning off SON.
Operation
Call the display screen after power on. Press the
“MODE” key to show the diagnostic screen.
Press “UP” twice.
Press “SET” for longer than 2 seconds.
Switch on/off the signal below the lit segment.
Indicates on/off output signal. The correspondence
between segments and signals are shown.
Press “MODE” once.
Shift to the upper segment of DO2.
Press “UP” once.
DO2 would light up.
Press “DOWN” once.
DO2 would light up.
Press “SET” more than 2 seconds.