Chapter 9 Product Specification
56
Shield M10U user manual
Chapter 9 Product Specification
This chapter provides UPS product specification.
9.1 Applicable Standards
The UPS has been designed to conform to the following European and international standards:
Table.9- 1: Compliance with European and International Standards
Item
Normative reference
General safety requirements for UPS used
in operator access areas
EN50091-1-1/IEC62040-1-1/AS 62040-1-1
Electromagnetic
compatibility
(EMC)
requirements for UPS
EN50091-2/IEC62040-2/AS 62040-2(C3)
Method of specifying the performance and
test requirements of UPS
EN50091-3/IEC62040-3/AS 62040-3(VFI SS 111)
Note:
The above mentioned product standards incorporate relevant compliance clauses with generic IEC and EN
standards for safety (IEC/EN/AS60950), electromagnetic emission and immunity (IEC/EN/ AS61000 series) and
construction (IEC/EN/AS60146 series and 60950).
9.2 Environmental Characteristics
Table.9- 2: Environmental Properties
Items
Unit
Requirements
Acoustic noise level at 1 meter
dB
56.0(power module)
Altitude of Operation
m
≤1000m above sea level, derate power by 1% per 100m between
1000m and 2000m
Relative Humidity
%RH
0 to 95%, non condensing
Operating Temperature
°C
0 to 40 deg , Battery life is halved for every 10°C increase above
20°C
UPS
Storage-Transport
Temperature
°C
-20~70
Recommended Battery Storage
Temperature
°C
0~25 (20°C for optimum battery storage)
9.3 Mechanical Characteristics
Table.9- 3: Mechanical Properties
Cabinet Specification
Unit
20/10
40/10
60/10
Mechanical
Dimension, W×D×H
mm
446×697×398(7U)
446×697×575(11U)
485*751*1033
Weight
kg
42
51
70
Color
N/A
Black
Protection
Level,
IEC(60529)
N/A
IP20
Module type
Unit
10
Mechanical
Dimension,
W×D×H
mm
436×590×85
Weight
kg
15.3
Color
N/A
Black(front)