Instruction Manual of A9060T Manual Call Points
------ Please read this Manual carefully before installing and using the product. -----
I. Overview
The A9060T manual call point
(
hereinafter referred to A9060T
)
is mainly designed to be used with an
intelligent two-bus control system. If it is pressed after a fire is manually confirmed, an alarm signal may
be sent to a fire alarm control system which will, after receiving the alarm signal, display the coded
address and the equipment status of the manual fire call points. When the manual fire call points is
operating normally, the red indicator will blink; when there is a fire alarm, it will remain lit. The A9060T
supports electronic coding, more suitable for engineering application convenient.
II. Product characteristics
ü
Semi-flush or surface mounting
ü
Compatible with the latest EN standards
ü
Lever reusable (non-glass break)
ü
LED indicator
ü
Full electronic coding, through CODER-9001 encoder scene rewrite
III. technical parameters
1.Executive Standard
:
EN54-11
2.Protection class
:
IP43
3.Operating voltage
:
24V (pulse modulation)
4.Operating Current
:
monitoring status <300uA, alarm status <2mA
5.Application
:
For indoor use
6.Operating temperature
:
-10
℃
~ 55
℃,
Relative humidity
:
≤
95% (non-condensing)
7.Indicator
:
Red alarm indicator flashes when data logging, press the manual button lit work
8.Encoding
:
coded by the encoder, the address range from 1 to 324 optional
9.Materials and colors
:
ABS, red
10.Wiring
:
The Promise of two bus system (L1, L2)
11.Size
:
90mm
×
90mm
×
42mm (overall height) / 90mm
×
90mm
×
23mm (exposed after installation
dimensions)
12.Mating Host
:
SEC3002 fire alarm control panel
13.Weight
:
about 95g
Fig. 1
Main part
IV. Mounting base
A9060T
should comply with all local codes, NFPA70 National Electrical Code, BS5389 and EN54.Shown
in Figure 2, the first one embedded box buried in the wall where the
A9060T
and then fixed to the base of
the embedded box.