AYXP9GHR

3 – 16

Indoor/
outdoor 
units in 
complete 
shutdown

11

times

11

-0

Outdoor unit DC 
fan

Outdoor unit DC fan 
rotation error

(1)

Check connector CN3 of 
the outdoor unit DC fan 
motor for secure installa-
tion.

(1)

Correct the installa-
tion.

(2)

Check the outdoor unit fan 
motor for proper rotation.

(2)

Replace the outdoor 
unit fan motor.

(3)

Check fuse FU3.

(3)

Replace the outdoor 
unit control PWB 
assembly.

(4)

Outdoor unit control PWB

(4)

Replace the outdoor 
unit control PWB 
assembly.

Indoor/
outdoor 
units in 
complete 
shutdown

13

times

13

-0

DC compressor

Compressor startup 
error

(1)

Check the colors (red, 
white, orange) of the com-
pressor cords for proper 
connection. (PWB side, 
compressor side)

(1)

Correct the installa-
tion.
(U: Red, V: White, W: 
Orange)

-1

Compressor rota-
tion error
(120

°

 energizing 

error)

(2)

Check if the IPM terminal 
resistance values are uni-
form.

(2)

Replace the outdoor 
unit control PWB 
assembly.

(3)

No abnormality found in 
above inspections (1) and 
(2).

(3)

Replace the outdoor 
unit control PWB 
assembly.

(4)

No abnormality found in 
above inspections (1) 
through (3).

(4)

Replace the compres-
sor.

Indoor/
outdoor 
units in 
complete 
shutdown

14

times

14

-0

Outdoor unit 
PAM

PAM over voltage 
error
Compressor rota-
tion error

(1)

Check the AC power sup-
ply voltage for fluctuation.

(1)

Connect stable power 
supply.

(2)

No abnormality found in 
above inspection (1).

(2)

Replace the outdoor 
unit control PWB 
assembly.

Indoor/
outdoor 
units in 
operation

-1

PAM clock error

(1)

Check the PAM clock for 
proper input.

(1)

Replace the outdoor 
unit control PWB 
assembly.

Indoor 
unit in 
operation
Outdoor 
unit in 
complete 
shutdown

17

-0

Wires between 
units

Serial open-circuit

(1)

Check the wires between 
units.

(1)

Connect stable power 
supply.

(2)

Check voltage between 
Nos. 1 and 2 on the 
indoor/outdoor unit termi-
nal boards.

(2)

Replace the outdoor 
unit control PCB 
assembly.

Outdoor unit does 
not turn on due to 
erroneous wiring

(1)

Check the wires between 
units.

(1)

Correct the wiring.

(2)

Check the outdoor unit 
fuse.

(2)

Replace the fuse/out-
door unit control PCB 
assembly.

(3)

Check 15-V, 13-V and 5-V 
voltages on the PWB.
Check resistance between 
IPM terminals.

(3)

Replace the outdoor 
unit control PCB 
assembly.

(4)

Check pins No. 5 and 7 of 
connector CN3 of the out-
door unit fan motor for 
short-circuit.

(4)

Replace the outdoor 
unit fan motor.

(5)

Outdoor unit control PCB

(5)

Replace the outdoor 
unit control PCB 
board.

18

-0

Serial short-circuit

(1)

Check the wires between 
units.

(1)

Correct the wiring.

-1

Serial erroneous wir-
ing

(1)

Check the wires between 
units.

(1)

Correct the wiring.

Status of 

indoor/

outdoor 

units

Indication 

by LED1 

on out-

door unit 

*2

Malfunction 

No. dis-

played on 

main unit 

display sec-

tion *1

Content of diagnosis

Inspection location/method

Remedy

Main 
cate-

gory

Sub-

cate-

gory

Main category

Sub-category

Содержание AE-X12GHR

Страница 1: ...RTS CHECK METH OD 3 8 7 OUTDOOR UNIT CHECK METHOD 3 10 8 TROUBLESHOOTING GUIDE 3 13 REPLACEMENT PARTS LIST SERVICE MANUAL AYXP9GHR CONTENTS Parts marked with are important for maintaining the safety of the set Be sure to replace these parts with specified ones for maintaining the safety and performance of the set This document has been published to be used for after sales service only The contents...

Страница 2: ...l 5RS092XDF Oil charge 320cc RB68A or Freil Alphc 68M Refrigerant system Evaporator Louver Fin and Grooved tube type Condenser Corrugate Fin and Grooved tube type Control Expansion valve Refrigerant R410A 1000g De lce system Micro computer controled reversed systems Noise level at cooling High dB A 42 46 Low dB A 37 Soft dB A 26 Fan system Drive Direct drive Air flow quantity at cooling High m3 mi...

Страница 3: ...B68A or Freil Alphc 68M Refrigerant system Evaporator Louver Fin and Grooved tube type Condenser Corrugate Fin and Grooved tube type Control Expansion valve Refrigerant R410A 1000g De lce system Micro computer controled reversed systems Noise level at cooling High dB A 43 49 Low dB A 39 Soft dB A 27 Fan system Drive Direct drive Air flow quantity at cooling High m3 min 10 7 30 2 Low m3 min 9 3 Sof...

Страница 4: ...AYXP9GHR 1 3 2 EXTERNAL DIMENSION 1 Indoor unit 2 Outdoor unit 278 198 790 22 0 58 18 5 175 INVERTER AIR CONDITIONER 265 780 540 14 165 540 299 72 58 37 5 12 4 5 324 135 81 136 ...

Страница 5: ... Indoor fan motor capacitor Transformer FUSE1 QFS GA062JBZZ 250V 3 15A FUSE2 QFS GA063JBZZ 250V 2A DESCRIPTION MODEL REMARKS Compressor 5RS092XDF D C brush less motor Outdoor fan motor ML A902 DC Motor Outdoor fan motor capacitor Fu4 QFS GA064JBZZ 250V 1A Fu3 QFS GA051JBZZ 250V 2A Fu2 QFS GA052JBZZ 250V 3 15A Fu1 QFS CA001JBZZ 250V 20A Fu5 6 QFS CA002JBZZ 250V 15A ...

Страница 6: ...to 10 minutes after self diagnosis is performed during operation and the display returns to normal condition after this display period The content of self diagnosis cannot be called out by the self diagnosis display function of the outdoor unit Example of self diagnosis display on outdoor unit Compressor high temperature error c The content of diagnosis is transferred to the indoor unit via serial...

Страница 7: ...ion 4 Temporary stop due to 2 way valve freeze 3 Temporary stop for cycle pro tection Indoor unit in operation Outdoor unit in tempo rary stop 3 times 3 0 Dry operation Temporary stop due to dehumidifying operation 3 Temporary stop for cycle pro tection Indoor outdoor units in complete shutdown 5 times 5 0 Outdoor unit thermistor open circuit Heat exchanger thermistor open cir cuit error 1 Check c...

Страница 8: ...r unit fan motor 3 AC current defi ciency error 1 Check if there is an open circuit in the secondary winding of the current transformer of the outdoor unit control PWB 1 Replace the outdoor unit control PWB assembly 2 Check if the refrigerant volume is abnormally low 2 Charge the specified amount of refrigerant 3 Check if the refrigerant flows properly 3 Correct refrigerant clogs 2 way valve 3 way...

Страница 9: ...er supply 2 No abnormality found in above inspection 1 2 Replace the outdoor unit control PWB assembly Indoor outdoor units in operation 1 PAM clock error 1 Check the PAM clock for proper input 1 Replace the outdoor unit control PWB assembly Indoor unit in operation Outdoor unit in complete shutdown 17 0 Wires between units Serial open circuit 1 Check the wires between units 1 Connect stable power...

Страница 10: ...t control PWB Indoor outdoor units in operation 20 0 Indoor unit con trol PCB EEPROM data error EEPROM read data error Replace the indoor unit control PWB Indoor outdoor units in operation 88 Control and dis play PCB Communication error 1 Check for disconnected connector between control PCB and display PCB and open circuit in lead wires 1 Insert connectors cor rectly or replace con trol PWB 2 Chec...

Страница 11: ...malfunction code is called out 3 Indoor unit relay Malfunction diagnosis display Relays turns Off after about 30 minutes None Displays 18 0 when malfunction code is called out 4 Indoor unit relay Malfunction diagnosis display Turns On momentarily then turns Off 18 1 5 Indoor unit relay Malfunction diagnosis display Turns On momentarily then turns Off 18 1 Indoor unit Outdoor unit 1 N 2 1 N 2 Indoo...

Отзывы: