Страница 2: ...Troubleshooting Quick Guide Sanicom 2 Lifting Station ...
Страница 3: ... from solids or grease good practice is have a dishwasher connected to pump if grease might be an issue Sanicom 2 lifting stations can be affected by poor installation or other usage issues This troubleshooting guide is also available as a PDF download on the Plumber Portal where you accessed this guide If you don t find your issue covered here please call our technical hotline numbers at end of p...
Страница 4: ...warmth as an indictor Motor will try restart after approx 45 60 mins Look for origin of overheating possible blockages in pump line Blocked pressure tubes due to fat or grease or faulty pressure switch Remove clear pressure tubes Check replace pressure switch if needed Call Saniflo technical for further assistance Symptom The motor does not activate No noise Given that Sanicom 2 has two motors we ...
Страница 5: ... and impeller Test and replace capacitor Motor windings failure Electrician to test windings and replace motor if required Symptom The motor hums but does not run activate Sanicom 2 Troubleshooting Guide Given that Sanicom 2 has two motors we need to clarify that one or both motors are still working This can be done by pressing the motor override buttons for each motor on the main control panel ...
Страница 6: ...tallation is over the specification or too many bends elbows Check installation The integral non return valve NRV is blocked faulty damaged Check clean replace integral NRV Blocked relief prime hole Clear the blockage from the relief prime hole Split internal discharge pipe rubber Replace if necessary Defective control board Consult Saniflo technical department Symptom The motor runs continuously ...
Страница 7: ...if needed repair the fixtures connected to the pump The integral non return valve NRV is blocked faulty damaged Check clean replace integral NRV Defective control board Consult Saniflo technical department Symptom The motor activates intermittently Sanicom 2 Troubleshooting Guide ...
Страница 8: ...charge line pinched Check impeller pump cover plate Discharge line Blocked relief prime hole Clear the blockage from the relief prime hole Partially blocked drainage fixture line or sink trap Check drain lines traps and clear blockages The length or height of the installation is over the specification or too many bends elbows Check installation Symptom Bad or very slow evacuation Sanicom 2 Trouble...
Страница 9: ...ce or lower pump Bad smell Accumulation of grease fats inside pump Clean service the pump Good practice is to have dishwasher connected to the pump Pump not vented to atmosphere Vent to atmosphere or install 2 way carbon block filter Plastec Ecovent or Studor Maxi Filtra Leaking from vent opening Blocked relief prime hole Clear the blockage from the relief prime hole Sanicom 2 Troubleshooting Guid...
Страница 10: ...Sanicom 2 Troubleshooting Guide Alarm Instructions troubleshooting guide ...
Страница 11: ... and kitchens anywhere and without major work Our products are manufactured in France and comply with the strictest requirements and consistently exceed customer expectations To maintain our high level of excellence our R D and engineers are constantly developing state of the art products to suit any projects from light domestic to heavy commercial applications ...
Страница 12: ...ANY MORE QUESTIONS Call Saniflo Head Office Australia 1300 554 779 NZ 0800 107 264 ...