Selection of Parameter P2-01, Digital Input Function
Parameters
8.3.5
Real-time monitoring parameters
Parameter group zero provides access to internal drive parameters for monitoring pur-
poses. These parameters cannot be adjusted.
Par.
Description
Display range
Explanation
P0-01
Bipolar analog input value
–100 % ... 100 %
100 % = max input voltage
P0-02
2nd analog input value
0 ... 100 %
100 % = max input voltage
P0-03
Speed controller reference
–500 % ... 500 %
100 % = Base frequency (P1-09)
P0-04
Digital speed ref (digi pot)
– P1-01 … P1-01
Speed displayed in Hz / rpm
P0-05
Torque controller reference
0 ... 200 %
100 % = motor rated torque
P0-06
User PID ref input
0 ... 100 %
PID controller reference value
P0-07
User PID feedback
0 ... 100 %
PID controller feedback value
P0-08
User PID error input
0 ... 100 %
Reference – Feedback
P0-09
User PID P-term
0 ... 100 %
Proportional component
P0-10
User PID I-term
0 ... 100 %
Integral component
P0-11
User PID D-term
0 ... 100 %
Differential component
P0-12
User PID output
0 ... 100 %
Combined output
P0-13
Output Torque
0 ... 200 %
100 % = motor rated torque
P0-14
Magnetizing current
A rms
Magnetizing current in A rms
P0-15
Rotor current
A rms
Rotor current in A rms
P0-16
Field strength
0 ... 100 %
Magnetic field strength
P0-17
Stator resistance
Ohm [
Ω
]
Phase - Phase stator resistance
P0-18
Stator inductance
H
Stator inductance in Henry
P0-19
Rotor resistance
Ohm [
Ω
]
Calculated rotor resistance
P0-20
DC bus voltage
V DC
Internal DC bus voltage
P0-21
Drive temperature
°C
Internal drive temperature
P0-22
Supply voltage L1 – L2
V rms, ph-ph
Phase – phase supply voltage
P0-23
Supply voltage L2 – L3
V rms, ph-ph
Phase – phase supply voltage
P0-24
Supply voltage L3 – L1
V rms, ph-ph
Phase – phase supply voltage
P0-25
Estimated Rotor speed
Hz or rpm
Applies to vector modes only
P0-26
kWh meter
0.0 … 999.9 kWh
Cumulative energy consumption
P0-27
MWh meter
0.0 … 60000 MWh
Cumulative energy consumption
P0-28
Software ID, IO processor
e.g. “1.00”, “493F”
Version number and check sum
P0-29
Software ID, Motor control
e.g. “1.00”, “7A5C”
Version number and check sum
P0-30
Drive serial number
000000 … 999999 00-000 … 99-999
Unique drive serial number
e.g. 540102 / 24 / 003
P6..
P60.
P600