Operating Instructions – MOVITRAC® B
5
Starting the motor in manual mode
Startup
5.6.2
Fixed setpoints
The following table shows which signals must be present on terminals X12:1 – X12:6
(DIØØ – DIØ5) when the "unipolar/fixed setpoint" setpoint is selected (
P100
) in order to
operate the drive with the fixed setpoints. This terminal assignment is an example. It can
be changed via parameters
P601 – 608
. CW/stop DIO1 is permanently assigned.
Function
X12:1 (DIØØ)
/Controller
inhibit
1)
X12:2 (DIØ1)
CW/stop
2)
X12:3 (DIØ2)
CCW/stop
X12:4 (DIØ3)
Enable/Stop
X12:5 (DIØ4)
n11/n21
X12:6 (DIØ5)
n12/n22
Controller inhibit
0
X
X
X
X
X
Stop
1
X
X
0
X
X
Enable and stop
1
0
0
1
X
X
Clockwise at n11
1
1
0
1
1
0
Clockwise at n12
1
1
0
1
0
1
Clockwise at n13
1
1
0
1
1
1
Counterclockwise
at n11
1
0
1
1
1
0
1) No default setting
2) Fixed assignment
0 = 0 signal
1 = 1 signal
X = Not relevant