![SEW movifit mc Скачать руководство пользователя страница 138](http://html1.mh-extra.com/html/sew/movifit-mc/movifit-mc_operating-instructions-manual_1249995138.webp)
7
Operation
MOVIFIT® MC status LEDs
Operating Instructions – MOVIFIT
®
MC
138
7.1.6
Option-specific LEDs
PROFIsafe option S11
WARNING
Observe the "MOVIFIT
®
MC/FC – Functional Safety" manual when using the
PROFIsafe option S11.
Severe or fatal injuries may result.
• If you use the PROFIsafe option S11, observe the additional notes on diagnos-
tics and operation as well as the safety conditions specified in the
"MOVIFIT
®
MC/FC – Functional Safety" manual.
WARNING
Danger due to incorrect interpretation of the "FDI.", "FDO.", "STO" and "F-STATE"
LEDs.
Severe or fatal injuries.
• The LEDs are not safety-related and may not be used as a safety device.
This chapter describes the option-specific LEDs for PROFIsafe option S11. In the fol-
lowing figure, these LEDs are shown as dark. In the sample figure, the PROFIBUS
version is shown with "Technology" function level:
DI03
DI01DI02
DI00
DI04DI05DI06DI07
DI08DI09DI10DI1
1
DI12/DO00
DI13/DO01
DI14/DO02
DI15/DO03
®
MOVIFIT
SF/USR
BUS-F
RUN
F-ST
A
TE
FDI00FDI01FDI02FDI03FDO00
FDO01
ST
O
24V
-C
24V
-S
9007200284854539
"FDI.." LEDs
The following tables show the statuses of the "FDI00" – "FDI03" LEDs.
LED
Meaning
Yellow
Illuminated
HIGH level at input F-DI..
Off
LOW level at input F-DI.. or open
"FDO.." LEDs
The following tables show the statuses of the "FDO00" – "FDO01" LEDs:
LED
Meaning
Yellow
Illuminated
F-DO.. output is active.
Off
F-DO.. output is inactive (switched off).
19484828/EN – 01/2015