5
Single-point synchronization
Operation
Product Manual – MOVITRANS
®
TES31A Decentralized Supply Unit Synchronization
50
5.6.2
Setting a setpoint
Only the master can modify a setpoint. Depending on the selected setpoint source in
the "Setpoint selection" window, the setpoint may be specified either with SBus pro-
cess data or in the "Fixed setpoints" window. As soon as the enable signal has been
sent to the master, the setpoint that has been set in the master is transmitted to the
slaves. The slaves then display the setpoint under "Active setpoint" in the Process val-
ues window.
Proceed as follows when synchronizing three stations:
1.
CAUTION!
Exceeded nominal current. Destruction of the line cables and pick-
ups.
The maximum set setpoint for three synchronization stations must not exceed
94%.
2. Set the setpoint input in the master to 94% to provide a resulting line cable current
of 85 A and to limit the load current per station to approx. 28 A.
5.6.3
Typical process values
The typical process values for a synchronization station are shown below:
SP master configuration
30901544715
29190657/EN – 04/2020