MOVITRAC® 07 electronics data
Technical Data
3.4
MOVITRAC
®
07 electronics data
Function
Terminal
Name
Data
Setpoint input (differential
input)
X10:13
X10:14
AI11 (+)
AI12 (0)
0 ... +10 V (R
i
> 200 k
Ω
)
0 ... 20 mA / 4 ... 20 mA (R
i
= 250
Ω
)
Resolution 10 bit, sampling interval 1 ms
Internal setpoints
n11/n12/n13 and n21/n22/n23 = 0 ... +5000 rpm
Auxiliary supply output
X10:1
VO24
V = 24 V
DC
, current carrying capacity I
max
= 50 mA
Binary inputs
X10:2
...
X10.6
DI01
...
DI05
R
i
= 3 k
Ω
, I
E
= 10 mA, sampling interval 5 ms, PLC compati-
ble
Signal level to EN 61131-2 type 1:
•
+13 ... +30 V
→
1 / contact made
•
–3 ... +5 V
→
0 / contact not made
Terminal assignment:
•
X10:2 / DI01 with fixed assignment CW/STOP
•
X10:5 / DI04 can be used as frequency input
•
X10:6 / DI05 can be used for TF (not at same time as fre-
quency input)
Supply voltage for TF
X10:7
VOTF
Relay output
X10:8
X10:9
X10:10
DO01-C
DO01-NO
DO01-NC
Shared relay contact
NO contact
NC contact
Load capacity: V
max
= 30 V, I
max
= 800 mA
Binary output
X10:11
DO02
PLC compatible, response time 5 ms, I
max
= 150 mA
Terminal response times
Binary input and output terminals are updated every 5 ms
System bus
1
1
SC21 and SC22 are deactivated when S12 = ON. This is necessary in units at the end of the bus.
X10:16
X10:17
X10:19
X10:20
SC11
SC12
SC21
SC22
Incoming, high
Incoming, low
Outgoing, high
Outgoing, low
CAN bus to CAN specification 2.0, parts A and B
•
Transmission system to ISO 11898
•
Shielded 2-core twisted cable
•
max. 64 stations
•
Terminating resistor (120
Ω
) can be activated via DIP
switch S12
Reference terminals
X10:12
X10:15
X10:18
X10:21
GND
Reference potential for binary and analog signals
Maximum line cross sec-
tion
1.5 mm
2
(AWG15) without conductor end sleeves
1.0 mm
2
(AWG17) with conductor end sleeves
RS-485 interface (only for
service purposes)
X11
Only for service purposes, exclusively for point-to-point con-
nection
Max. cable length 3 m (10 ft)
S11 = Switch mode analog input I-signal / V-signal
S12 = System bus terminating resistor
S12
S11
X10
X11
P
i
f
kVA
Hz