9
Service
Cleaning
Operating Instructions – MOVIPRO
®
PHE..B-A15-.1X0..B-00
78
9.2.2
Replacing the device
Proceed as follows to replace the device:
1. De-energize the conductor rail, disconnect the device from the power supply, and
remove it from the plant.
2. Loosen the screw fitting of the M12 parameter memory and remove it from the
device.
3. Plug the M12 parameter memory into the X4441 plug connector of a new device
and tighten the screw.
4. Install the new device in the plant.
5. Switch the power supply back on.
For more information, refer to the "MOVIVISION
®
EMS basic" manual.
9.3
Cleaning
Before cleaning the device, disconnect it from the grid. Disconnect the conductor rail
from the power if required.
Clean the device only with solvent-free cleaning agent.
9.4
Status display
The status display shows status and error messages and thus enables you to record
the current state of the device.
For more information refer to chapter Status and error messages and the documenta-
tion on the user program (for the respective system solution). In case of questions,
contact SEW‑EURODRIVE.