![SEW-Eurodrive MOVIPRO ADC Скачать руководство пользователя страница 47](http://html.mh-extra.com/html/sew-eurodrive/movipro-adc/movipro-adc_operating-instructions-manual_1250122047.webp)
5
Project planning for devices with R15 regenerative power supply module
System configuration
Operating Instructions – MOVIPRO
®
ADC
47
5.3
System configuration
The following table shows the restrictions for different system configurations:
System configuration
Restrictions
TT/TN networks
None
IT systems
Prohibited
5.4
Notes on operation
Observe the following notes for the operation of the device with R15 regenerative
power supply module:
•
To avoid reactive power in the supply system, enable the R15 regenerative power
supply module only when the drives connected to the device are active.
•
While the regenerative power supply module is inhibited, the device must not be
operated in regenerative mode; otherwise, error "U
Z
overvoltage" is tripped.
•
Wait until all drives connected to the device have come to a standstill before you
inhibit the regenerative power supply module. Otherwise, the regenerative power
supply module cannot feed back any regenerative energy to the supply system.