Operation
Brake control operation
Operating Instructions – MOVIPRO
®
ADC
168
9.3
Brake control operation
NOTICE
Damage to the brake controller if necessary off periods are not adhered to.
Damage to the drive system.
•
Observe the required off periods for the brake controller.
9.3.1
Brake control under normal operating conditions, e.g. automatic operation of the plant
With a brake coil power of P ≥ 70 W, you must ensure a timeout of at least 1 second
for brake control:
toff
1s
toff
1s
toff
1s
toff
1s
ton
ton
ton
ton
t/s
Brake control
signal
2950935051
9.3.2
Brake control under special operating conditions, e.g. teach or jog mode
For teach or jog mode, for example, timeouts shorter than 1 second are possible. After
20 control pulses, a timeout of minimum 3 min is mandatory in this case.
t
toff min. 180 s
max. 20 impulses
Brake control
signal
2951034251
22749055/EN – 04/2016