7
Electrical installation
Electrical connections
Operating Instructions – MOVIPRO
®
ADC
140
7.12.24 X4232_11 and X4232_12: Ethernet fieldbus
Function
Ethernet fieldbus interface
Connection type
Push-pull RJ45
Wiring diagram
1
8
Assignment
No.
Name
Function
1
TX+
Transmit line (+)
2
TX-
Transmit line (-)
3
RX+
Receive line (+)
4
res.
Reserved
5
res.
Reserved
6
RX-
Receive line (-)
7
res.
Reserved
8
res.
Reserved
NOTICE
RJ45 patch cable without push-pull connector housing not snapped into place.
Damage to the push-pull RJ45 connection.
•
Only use push-pull RJ45 mating connectors in accordance with IEC PAS
61076-3-117.