15
Technical data
Technical data for field distributors
Manual – PROFINET IO Interfaces, Field Distributors
176
15.2
Technical data for field distributors
15.2.1
MF../Z.3 field distributor
MF../Z.3.
Max. permitted total current X1
(Terminals X1: line connection)
32 A
Max. permitted total current X21
(Terminals X21: 24 V power bus)
32 A
Max. permitted total current X20
(Terminals X20: 24 V distributor termin-
als)
12 A
Ambient temperature
-25 °C – 60 °C
Storage temperature
-25 °C – 85 °C
Degree of protection
IP65 (fieldbus interface and motor connection cable attached and
fastened, all plug connections sealed)
Interface
PROFIBUS, PROFINET IO, EtherNet/IP™, EtherCAT
®
,
DeviceNet™
Permitted motor cable length
max. 30 m (with SEW‑EURODRIVE hybrid cable, type B)
for cross section reduction compared to the supply system cable
Note the line fusing.
Mass
Approx. 1.3 kg
15.2.2
MF../Z.6. field distributor
MF../Z.6.
Max. permitted total current X1
(Terminals X1: line connection)
32 A
Max. permitted total current X21
(Terminals X21: 24 V power bus)
32 A
Max. permitted total current X20
(Terminals X20: 24 V distributor termin-
als)
12 A
Maintenance switch
Switch disconnector and line protection
Type: ABB MS 325 – 9 + HK20
Switching: black/red, triple lock
Ambient temperature
-25 °C – 55 °C
Storage temperature
-25 °C – 85 °C
Degree of protection
IP65 (fieldbus interface, power supply connection cover and mo-
tor connection cable attached and fastened, all plug connections
sealed)
Interface
PROFIBUS, PROFINET IO, EtherNet™, EtherCAT
®
, DeviceNet™
Permitted motor cable length
max. 30 m (with SEW‑EURODRIVE hybrid cable, type B)
22870857/EN – 12/2016