11
Technical data and dimension sheets
Technical data
Operating Instructions – MOVIGEAR
®
performance
309
11.3.3
Derating factors
Derating depending on the ambient temperature
The following figure shows the I
N
reduction depending on the ambient temperature:
Ambient temperature
in °C
Motor current rms value
N
in % of I
25580747147
I
N
reduction:
3% I
N
per K at 40 °C to 60 °C
Derating depending on the installation altitude
Observe the derating according to the chapter "Mechanical installation" > "Setting up
the drive unit" > "Derating depending on the installation altitude".
Notes
INFORMATION
Derating is based on typical operating conditions with a supply voltage of 24 V
(sensor supply, input voltage of STO input).
11.3.4
Current-carrying capacity of terminals
Current-carrying capacity of terminals
Line terminals
X1
24 A (max. loop-through current)
Control terminals
X9
10 A (max. loop-through current)
11.3.5
DC 24 V supply
Input for the independent backup voltage supply of the electronics
DC 24 V input
24V_IN
U
IN
= DC 24 V -10%/+20% according to EN 61131-2
Current consumption:
I
E
≤ 500 mA, typically 250 mA for electronics
•
Plus up to 100 mA for the safety option
•
Plus up to 100 mA for 2 digital outputs (50 mA each)
•
Plus up to 500 mA, for sensor supply
0V24_IN
25945475/EN – 04/2019