5
Electrical Installation
Installation instructions (all versions)
Operating Instructions – MOVIFIT
®
-FC
35
5.2.4
Notes on PE connection and/or equipotential bonding
Earth-leakage currents
Ã
3.5 mA may occur during normal operation. To meet the
requirements of EN 61800-5-1, observe the following note:
• Route a second PE conductor with the cross section of the supply system cable in
parallel to the protective earth via separate terminals, or use a copper protective
earth conductor with a cross section of 10 mm
2
.
DANGER
Incorrect connection of PE
Severe or fatal injuries or damage to property from electric shock
• The permitted tightening torque for the screw connection is 2.0-2.4 Nm (18-21 lb.in).
• Observe the following notes regarding PE connection:
Prohibited assembly procedure
Recommendation: Assembly with forked
cable lug
Permitted for all cross sections
Assembly with solid connecting wire
Permitted for cross sections up to
max. 2.5 mm
2
323042443
323034251
323038347
[1] Forked cable lug suitable for M5 PE screws
[1]
M5
2.5 mm²
M5