9
Technical Data
Version with operating point 460 V/60 Hz
132
Operating Instructions – MOVIFIT
®
-FC
9.3
Version with operating point 460 V/60 Hz
MOVIFIT
®
unit type
MTF11A
003-503
MTF11A
005-503
MTF11A
007-503
MTF11A
011-503
MTF11A
015-503
MTF11A
022-503
MTF11A
030-503
MTF11A
040-503
Size 1
Size 2
Apparent output power at
V
Mains
= AC 380-500 V
S
Rated
1.1 kVA
1.4 kVA
1.8 kVA
2.2 kVA
2.8 kVA
3.8 kVA
5.1 kVA
6.7 kVA
Supply voltages
Permitted range
V
Mains
AC 3 x 380 V / 400 V / 415 V /
460 V
/ 500 V
V
Mains
= AC 380 V –10% – AC 500 V +10%
Supply frequency
f
Mains
50-60 Hz ± 10%
Rated mains current
(with V
Mains
= AC 400 V)
I
Mains
AC 1.1 A
AC 1.4 A AC 1.7 A AC 2.1 A
AC 3.0 A AC 4.3 A
AC 5.8 A
AC 6.9 A
Output voltage
V
Output
0 – V
Mains
Output frequency
Resolution
Operating point
f
A
2-120 Hz
0.01 Hz
400 V at 50 Hz / 100 Hz
Rated output current
I
Rated
AC 1.6 A
AC 2.0 A AC 2.5 A
AC 3.2 A
AC 4.0 A AC 5.5 A
AC 7.3 A AC 8.7 A
Motor power S1
P
Mot
0.37 kW
0.5 HP
0.55 kW
0.75 HP
0.75 kW
1.0 HP
1.1 kW
1.5 HP
1.5 kW
2.0 HP
2.2 kW
3.0 HP
3.7 kW
5.0 HP
4.0 kW
5.4 HP
PWM frequency
4/8/
16
1)
kHz (
factory setting 16 kHz
)
1) 16 kHz PWM frequency (low-noise): The unit switches to lower cycle frequencies depending on the heat sink temperature and load.
Current limitation
I
max
motor:
160% at
Õ
and
Ö
regenerative:
160% at
Õ
and
Ö
External braking resistor
R
min
150
Ê
68
Ê
Cable length between
MOVIFIT
®
and motor
Max. 15 m (with SEW hybrid cable, type A)
Hybrid cable shielding
Apply outer shield with EMC cable gland; apply inner shield with EMC shield clamp
(see section "Installation Instructions").
Interference immunity
Fulfills EN 61800-3
Interference emission
Limit value class C3 to EN 61800-3
Motor protection
Thermistor
Operating mode
S1 (EN 60034-1), S3 max. cycle duration 10 minutes
Cooling type (DIN 41751)
Self-cooling
Degree of protection
Standard:
IP65 in accordance with EN 60529 (MOVIFIT
®
housing closed and all cable bushings and
plug connections sealed)
Hygienic
plus
version:
IP66 in accordance with EN 60529 and IP69K in accordance with DIN 40050-9 (MOVIFIT
®
housing closed and all cable bushings sealed according to the relevant degree of protection)
Ambient temperature
–25°C to +40°C (P
Rated
reduction: 3% I
Rated
per K to max. 60°C)
Climate class
EN 60721-3-3, class 3K3
Storage temperature
2)
2) If the unit is being stored for a long time, connect it to the mains voltage for at least 5 minutes every 2 years. Otherwise, the unit's
service life may be reduced.
–25°C to +85°C (EN 60721-3-3, class 3K3)
Permissible oscillation and
impact load
According to EN 50178
Overvoltage category
III according to IEC 60664-1 (VDE 0110-1)
Pollution class
2 according to IEC 60664-1 (VDE 0110-1) within the housing
Installation altitude
h
Up to 1,000 m without restrictions
(installation altitude at 1000 m and higher: see section "Installation instructions")
Mass
EBOX "MTF...-....-00" (MOVIFIT
®
-FC) size 1: Approx. 3.5 kg
EBOX "MTF...-....-00" (MOVIFIT
®
-FC) size 2: Approx. 5.6 kg
ABOX "MTA...-S02.-...-00": Approx. 4.5 kg
ABOX "MTA...-S42.-...-00", "MTA...-S52.-...-00", "MTA...-S62.-...-00": Approx. 4.8 kg
ABOX "MTA...-H12.-...-00", "MTA...-H22.-...-00": Approx. 6.0 kg
P
i
f
kVA
Hz
n