7
Operation
Status LEDs for MOVIFIT®-FC
112
Operating Instructions – MOVIFIT
®
-FC
"SF/USR" LED
The "SF/USR" LED indicates the various statuses depending on the function level.
The following table shows the statuses of the "SF/USR" LED:
SF/USR
Function
level
Meaning
Remedy
C
T
S
Off
•
Standard operating state:
MOVIFIT
®
exchanges data with
the connected drive system
(integrated inverter).
-
Red
•
MOVIFIT
®
cannot exchange
data with an integrated inverter.
Check the DC 24 V supply of the integrated
inverter.
Flashing
red
(2 s
cycle)
•
MOVIFIT
®
initialization error or
serious unit fault
Incorrect card ID
Switch on MOVIFIT
®
again. If the fault is still
present, replace the EBOX or contact SEW
Service.
Flashing
red
•
Other unit faults
Use MOVITOOLS
®
MotionStudio to read out
the fault status.
Remedy the cause of and acknowledge the
fault.
Off
•
IEC program is running.
-
Green
•
IEC program is running.
The IEC program controls the
green LED.
For the meaning, see the IEC program
documentation.
Red
•
Due to an error, boot project was
cancelled or did not start.
Use MOVITOOL
®
/PLC Editor/Remote Tool to
log on; start the boot project.
•
MOVIFIT
®
initialization fault
Incorrect EBOX/ABOX combina-
tion
Incorrect card ID
Check the type of MOVIFIT
®
-EBOX. Place
the correct EBOX in the ABOX and perform
the complete startup process.
Flashing
red
•
No IEC application program
loaded
Load an IEC application program and, if
necessary, restart the integrated PLC.
Flashing
yellow
•
The IEC application program
has been loaded, but it is not
running (PLC = Stop).
Check the IEC application program using
MOVITOOLS
®
MotionStudio and, if neces-
sary, restart the integrated PLC.
Flashing
1 x red
and
n x
green
•
Fault status reported by the IEC
program
For status/rectification, see the IEC program
documentation.
Red
•
MOVIFIT
®
displays a fault
status.
Eliminate the cause of the fault and use
PROFIBUS to acknowledge the fault mes-
sage. Use MOVIVISION
®
for detailed fault
diagnostics.
Flashing
red
•
MOVIFIT
®
indicates a fault
status; cause of fault has
already been eliminated.
Use PROFIBUS to acknowledge the fault
message. Use MOVIVISION
®
for detailed
fault diagnostics.
•
Valid for selected function level:
C = Function level "Classic"
T = Function level "Technology"
S = Function level "System"
Содержание MOVIFIT-FC