5
Electrical installation
Standard ABOX MTA...-S02.-...-00
Operating Instructions – MOVIFIT
®
FC
68
X8, X81, X9 and X91: Motor connection terminals
WARNING
Risk of crushing due to incorrect parameterization of the digital output DB00.
Severe or fatal injuries.
• If digital output DB00 is used to control the brake, do not change the parameters
that define the functions of the digital output.
• Check the parameter settings before using the digital output to control the brake.
1
11
11 12
12 13
13 14
1415
15 16
16
2 3 4 5 6
17
1718
18
7 8
X29
1 2 3 4
X91
S3
1
11 12 13 14 15 16
2
3
4
5
6
X20
1
2
3
4
11 12 13 14
X1
11
1 2 3 4 5 6 7 8
12 13 14 15 16 17 18
31 32 33 34 35 36 37 38
21 22
11
1 2 3 4 5
12 13 14 15
31 32 33 34 35
21 22 23 24 25
11
1 2 3 4 5
12 13 14 15
23 24 25 26 27 28
X45
X25
X35
X50
5
6
7
5
1
1 2 3 4
2
3
4
1
2
3
4
6
7
X81
X8
X9
812534411
Motor connection terminals (connection via hybrid cable)
No.
Name
Function for motor with SEW stand-
ard brake
Function for motor with 2-wire constant DC
brake
1)
X8
1
PE
Motor PE connection
2
U
Motor phase U output
3
V
Motor phase V output
4
W
Motor phase W output
5
15
SEW brake terminal 15 (blue)
DC brake connection (+)
6
14
SEW brake terminal 14 (white)
No function
7
13
SEW brake terminal 13 (red)
DC brake connection (-)
X81
1
TF+
Connection for TF temperature sensor / TH temperature switch (+) motor
2)
2
TF-
Connection temperature sensor TF/temperature switch TH (-) motor
2)
3
DB00
Digital output "Brake released" = Factory setting (switching signal 24 V)
4
0V24_C
0V24 reference potential for brake output
X9
1
PE
PE connection
2
-
Reserved
3
-
Reserved
4
-
Reserved
5
-R
Braking resistor connection "-R"
6
-
Reserved
7
+R
Braking resistor connection "+R"
X91
1 – 4
-
Reserved
1) Before starting up the MOVIFIT® FC drive with constant DC brake, you must connect an additional external braking resistor to the
MOVIFIT® inverter.The braking resistor is used to dissipate the regenerative energy.
2) With motor without TF/TH, jumper X81/1 terminal must with X81/2 terminal.Then activate the electronic motor protection by setting
the parameter P340 and P342 to "ON".