5
Electrical installation
Standard ABOX MTA...-S02.-...-00
Operating Instructions – MOVIFIT
®
FC
66
5.6.5
Terminal assignment
WARNING
Electric shock due to dangerous voltages in the ABOX.
The maintenance switch disconnects only the integrated frequency inverter from the
power supply. Voltage is still present on the terminals of the MOVIFIT
®
unit.
• Switch off the power to the MOVIFIT
®
unit using a suitable external disconnecting
device, and wait at least 1 minute before opening the wiring space.
The terminal diagrams depicted in this chapter differ depending on the fieldbus sys-
tem used. The area dependent on the fieldbus is therefore represented as hatched
and is described in the following sections.
X1: Line terminals (power bus)
1
11
11 12
12 13
13 14
1415
15 16
16
2 3 4 5 6
17
1718
18
7 8
X29
S3
5
6
7
X81
X91
X20
X45
X25
X35
1
2
3
4
11
1 2 3 4 5 6 7 8
12 13 14 15 16 17 18
31 32 33 34 35 36 37 38
21 22 23 24 25 26 27 28
11
1 2 3 4 5
12 13 14 15
31 32 33 34 35
21 22 23 24 25
1
11 12 13 14 15 16
2
3
4
5
6
5
6
7
1 2 3 4
1
2
3
4
1 2 3 4
X50
11
1 2 3 4 5
12 13 14 15
X8
X9
1
2
3
4
11 12 13 14
X1
812531083
Line terminal (power bus)
No.
Name
Function
X1
1
PE
Line connection PE (IN)
2
L1
Line connection phase L1 (IN)
3
L2
Line connection phase L2 (IN)
4
L3
Line connection phase L3 (IN)
11
PE
Line connection PE (OUT)
12
L1
Line connection phase L1 (OUT)
13
L2
Line connection phase L2 (OUT)
14
L3
Line connection phase L3 (OUT)
21316996/EN – 12/2014