5
Electrical installation
Standard ABOX MTA...-S02.-...-00
Operating Instructions – MOVIFIT
®
FC
61
5.6.3
Additional installation instructions for MTA...-S02.-...-00
Permitted connection cross-section and current carrying capacity of the terminals
Terminal data
X1, X20
X8, X9
X25, X30, X31,
X35, X45, X81, X91
X29
Connection cross
section
0.2 – 6 mm
2
0.08 – 4
1)
mm
2
0.08 – 2.5
1)
mm
2
0.2 – 1.5
1)
mm
2
AWG 24 – AWG10 AWG 28 – AWG12
1)
AWG 28 – AWG14
1)
AWG 24 – AWG16
1)
Current carrying ca-
pacity (max. contin-
uous current)
X1: 32 A
X20: 16 A
20 A
10 A
10 A
Conductor stripping
length
13 – 15 mm
8 – 9 mm
5 – 6 mm
9 – 10 mm
1) The maximum permitted cross section is reduced by one unit when using conductor end sleeves (e.g. 2.5 → 1.5)
Conductor end sleeves
Use conductor end sleeves without plastic collar for terminals X1, X20, X8, and X9
(DIN 46228-1, material E-CU).
21316996/EN – 12/2014