7
Operation
Status LEDs MOVIFIT® FC
Operating Instructions – MOVIFIT
®
FC
149
7.1.2
Bus-specific LEDs for PROFIBUS
This chapter describes the bus-specific LEDs for PROFIBUS. In the following figure,
the LEDs are shown as dark:
D
I0
3
D
I0
1
D
I0
2
D
I0
0
D
I0
4
D
I0
5
D
I0
6
D
I0
7
D
I0
8
D
I0
9
D
I1
0
D
I1
1
D
I1
2/D
O
00
D
I1
3/D
O
01
D
I1
4/D
O
02
D
I1
5/D
O
03
SF
/U
SR
BU
S-F
24
V
-C
24
V
-S
R
U
N
®
MOVIFIT
R
U
N
PS
ST
O
9007200090845963
"BUS-F" LED
The following table shows the statuses of the "BUS-F" LED:
LED
Meaning
Measure
Off
MOVIFIT
®
is exchanging data
with the DP master (data ex-
change).
-
Red
Flashing
The baud rate is detected. How-
ever, MOVIFIT
®
is not being ad-
dressed by the DP master.
MOVIFIT
®
was configured incor-
rectly or not configured in DP
master.
• Check the project planning of the
DP master.
• Check whether all the modules
configured during project plan-
ning are permitted for the
MOVIFIT
®
variant used (MC, FC,
SC).
Red
Illuminated
Connection to the DP master has
failed.
MOVIFIT
®
does not detect baud
rate. Bus interruption
DP master not in operation.
• Check the PROFIBUS DP con-
nection of MOVIFIT
®
.
• Check the DP master.
• Check all cables in your
PROFIBUS DP network.
21316996/EN – 12/2014