DIP switch S10/3
Motor/brake type
• When you are using IEC or NEMA motors (DT/DV), DIP switch S10/3 must always
be set to OFF.
• For DX/DZ motors with rated voltages of 220/380 V, 60 Hz (only available in Bra-
zil), and for aseptic motors (DAS), DIP switch S10/3 must be set to ON.
• When you are using DR.. motors with MOVIFIT
®
standard brakes, DIP switch
S10/3 must always be set to OFF.
• When you are using DR.. motors with option brakes, DIP switch S10/3 must always
be set to ON.
DIP switch S10/4
Motor connection type
• DIP switch S10/4 = ON: You must select this setting if the motor is operated in del-
ta connection (refer to the tables on the following pages).
• DIP switch S10/4 = OFF: You must select this setting if the motor is operated in
star connection (refer to the tables on the following pages).
DIP switch S10/5
Lower motor power rating
• When activated, this DIP switch enables MOVIFIT
®
to be assigned to a motor with
a lower power rating. The nominal unit power is not affected.
• When using a motor with a lower power rating, the MOVIFIT
®
unit is one perform-
ance level above the motor. The overload capacity of the drive may be increased
as a result. A higher current can be provided briefly, leading to higher torque rat-
ings.
• The aim of switch S10/5 is to achieve short-term utilization of the motor's peak tor-
que. The unit's current level remains the same regardless of the switch setting.
Blocking protection for the motor is adjusted depending on the switch position.
• When DIP switch S10/5 is activated, the motor cannot be operated with stall pro-
tection.
INFORMATION
The type of connected brake can be found on the nameplate of the motor.
The braking torque of the brake is listed in chapter "Braking torques".