8
Service
Reset
Operating Instructions – MOVIFIT
®
compact
91
8.3
Reset
WARNING
Electric shock due to dangerous voltages in the ABOX.
Severe or fatal injuries.
•
De-energize the MOVIFIT
®
device. Observe the minimum switch-off time after
disconnection from the supply system:
–
1 minute
WARNING
Danger if the motor starts up unintentionally.
Fatal or severe injuries and damage to property.
•
Before starting the work, switch off the power to the MOVIFIT
®
device.
•
Safeguard the MOVIFIT
®
device from unintentional activation.
8.3.1
Manual reset
Depending on the current operating mode and the device type of the MOVIFIT
®
com-
pact device, a manual reset can be performed as follows:
Device type
Manual reset
in automatic
mode
1)
with the MBBG11A
operator panel
with
MOVITOOLS
®
MotionStudio
Frequency inverter
MBF07B-..
MBF11B-..
MBF15B-..
Set
DI0 and DI1 = 1.
Press the <STOP/RE-
SET> key.
Set parameter
P840
= 1.
Motor starter
MBS2RB-..
MBS4RB-..
MBS4DB-..
Set DI2 = 1.
Press the <STOP/RE-
SET> key.
Set parameter
P840
= 1.
1) With binary control or AS-Interface controller
22527060/EN – 08/2017