The MBBG11A operator panel displays the error codes that occur at the MOVIFIT
®
compact.
8.2.1
MOVIFIT
®
compact inverter error list
Code Subcode Meaning
Possible cause
Measure
F 01
0
Overcurrent in output stage Short circuit at in-
verter output
•
Check the connection between the
inverter output and the motor.
•
Check the motor winding for short
circuiting.
Sudden overload
of motor
•
Check motor shaft for blocking.
F 06
0
Phase failure
Failure of one or
more line phases
•
Check the supply system cable for
phase failure.
F 07
0
DC link voltage too high
Ramp time too
short
•
Extend the ramp time.
Non-permissible
line voltage range
•
Ensure that the line voltage is per-
missible for the device.
F 09
0
Motor startup error
Error during start-
up of motor in
PROFI mode
•
Check/correct the data that has been
entered.
•
Repeat the motor startup.
F 11
0
Thermal overload of output
stage
Cooling fins
soiled
•
Clean the cooling fins.
Ambient temper-
ature too high
•
Reduce the ambient temperature.
Heat build-up at
MOVIFIT
®
com-
pact device
•
Prevent heat build-up at the
MOVIFIT
®
compact device.
•
Check distance from neighboring
components.
Drive load too
high
•
Reduce the drive load.
F 18
13, 103
CPU error
-
•
Reset the error.
•
If the error persists, contact SEW-
EURODRIVE Service.
F 25
5, 7, 8,
203
EEPROM error
-
•
Load the factory settings and repeat
the startup.
F 36
0
MBBG11A timeout error
MBBG11A dis-
connected during
manual opera-
tion.
•
Plug in the plug connector of the MB-
BG11A operator panel again.
•
Reset the error.
F 37
0
Inverter software run-time
error
•
Contact SEW‑EURODRIVE Service.