172
System Manual – MOVIDRIVE® compact Drive Inverters
3
Operating modes
Parameters
VFC 1 / 2 & Group
Set this mode if a group of asynchronous motors is to be operated on one inverter. All
motors of the group must have the same rated voltage and rated frequency. The brake
is controlled via P730 Brake function 1 / P733 Brake function 2 . Set the data for the larg-
est motor in the group during startup. Following startup, P303 Current limit 1 / 313 Cur-
rent limit 2 have to be set to the total current of all connected motors. We recommend a
basic setting of P321 Boost 1 / P331 Boost 2 to the same value as P322 IxR compen-
sation 1 / P332 IxR compensation 2 .
Settings after the startup function
P303 Current limit 1 / P313 Current limit 2
I
max
(inverter) = 150 %
Σ
I
N_mot
P302 Maximum speed 1 / P312 Maximum speed 2
Depends on number of poles and rated
motor frequency
e. g. 2 pole / 50 Hz -> 3000 1/min
e. g. 4 pole / 60 Hz -> 1800 1/min
P301 Minimum speed 1 / P311 Minimum speed 2
15 1/min
P130 ... P133 Ramp t11 / P140 ... P143 Ramp t21
2 s
P136 Stop ramp t13 / P146 Stop ramp t23
2 s
P137 Emergency stop ramp t14 / P147 Emergency stop
ramp t24
2 s
P500 Speed monitoring 1 / P502 Speed monitoring 2
MOTOR & REGENERATIVE
P501 Deceleration time 1 / P503 Deceleration time 2
1 s
UNIPOL./FIX.SETPOINT
TERMINALS
P730 Brake function 1 / P733 Brake function 2
ON
P731 Brake release time 1 / P734 Brake release time 2
For SEW motors: Setting in accordance
with motor data.
For non-SEW motors: Set the correct
value manually!
P732 Brake application time 1 / 735 Brake application time 2
P300 Start/stop speed 1 / P310 Start/stop speed 2
Setting in accordance with specified data
P820 4-quadrant operation 1 / P821 4-quadrant operation 2
ON
NOTES
•
Do not use this operating mode for hoist applications.
•
The premagnetization current is adapted to the largest motor in the group during
startup. If motors are removed from the group by switching them off, it may be
necessary to reduce the current limit to a current that matches the actual combina-
tion of motors.
•
Slip compensation is not effective. Motor speeds are therefore dependent on the
load.
P6..
P60.
P600