PROFIBUS-DP-V1 Functions
Structure of the DP-V1 parameter channel
Manual – MOVI-PLC
®
basic DHP11B.. controller
63
Procedure for
setting
parameters via
data set 47
Parameter access is provided by the combination of the DP-V1 services
write
and
read
.
The master transfers the parameter setting request to the slave by sending
Write.req
.,
followed by slave-internal processing.
The master now sends a
Read.req
to request the parameter setting response. The
master repeats the
Read.req
if the
Read.res
from the slave is negative. As soon as
parameter processing is finished in the MOVI-PLC
®
basic
DHP11B.. controller (slave),
the controller answers with a positive
Read.res
. response. The user data now contains
the parameter setting response of the parameter setting request that was previously
sent with
Write.req
(
Æ
following figure). This telegram sequence applies to both a C1
and a C2 master.
58380AXX
Write.req DS47
Parameter
Parameter
Parameter
Parameter
Parameter
Read.req DS47
Read.req DS47
Write.res
Read.res(-)
Read.res(+)
with data (parameter request)
Request
Response
Response
Request
Processing
without data
without data
without data
without data
with data (parameter response)
Master
PROFIBUS-DP-V1
Slave (DHP11B)
0
0
I