Project Planning and Startup
Configuring a PROFIBUS-DP master
44
Manual – MOVI-PLC
®
basic DHP11B.. controller
Configuration
example
Slot 1: Empty
Slot 2: Param (4 words)
Slot 3: 10 PD
Configuration telegram sent to the MOVI-PLC
®
basic
DHP11B.. controller: 0x00 0xC0
0xC87 0x87 0xC0 0xC9 0xC9
Universal DP
configuration
After selecting the "Universal Module" DP configuration (S7 HW Config), you can struc-
ture the DP configuration individually, although the following basic conditions must be
adhered to:
Module 0 (DP identifier 0) defines the parameter channel of the control card.
To ensure the parameter settings are made correctly, you must always transfer the
parameter channel consistently for the entire length.
Module 1 (DP identifier 1) defines the process data channel of the control card.
In addition to the process data configuration predefined in the GSD file, you can also
specify process data configuration with 4, 5, 7, 8 and 9 process data words. Ensure that
the number of input and output words is always the same. If the lengths are different,
data cannot be exchanged. In this case, the
Profibus Fault
LED will continue to flash.
16 PD
Process data exchange via
16 process data words
0xC0, 0xCF, 0xCF
32 PD
Process data exchange via
32 process data words
0xC0, 0xDF, 0xDF
Process Data
Configuration
Meaning / Notes
DP configuration
Length
Function
0
Parameter channel deactivated
8 I/O bytes or 4 I/O words
Parameter channel is used
Length
Function
2 I/O bytes or 1 I/O word
1 process data word
4 I/O bytes or 2 I/O words
2 process data words
6 I/O bytes or 3 I/O words
3 process data words
8 I/O bytes or 4 I/O words
4 process data words
10 I/O bytes or 5 I/O words
5 process data words
12 I/O bytes or 6 I/O words
6 process data words
14 I/O bytes or 7 I/O words
7 process data words
16 I/O bytes or 8 I/O words
8 process data words
18 I/O bytes or 9 I/O words
9 process data words
20 I/O bytes or 10 I/O words
10 process data words