![SEW-Eurodrive MOVI-PLC basic DHP11B-T0 Скачать руководство пользователя страница 21](http://html.mh-extra.com/html/sew-eurodrive/movi-plc-basic-dhp11b-t0/movi-plc-basic-dhp11b-t0_manual_1250108021.webp)
3
Assembly / Installation Instructions
Installation of MOVI-PLC® basic DHP11B.. controller
Manual – MOVI-PLC
®
basic DHP11B.. controller
21
3.4.6
Operating displays of the MOVI-PLC
®
basic DHP11B.. controller
The MOVI-PLC
®
basic
DHP11B.. controller comes equipped with seven LEDs that indi-
cate the current status of the MOVI-PLC
®
basic
DHP11B.. controller and its interfaces.
24V / I/O OK LED
The
24 V / I/O OK
LED indicates the status of the voltage supply for binary
inputs/outputs.
LED 24V / I/O OK
PLC status LED
IEC program status LED
Run Profibus LED
Fault Profibus LED
CAN 2 status LED
CAN 1 status LED
DHP11B
X31
X32
X33
1
3
1
2
3
1
2
3
2
1
2
3
1
2
3
24V / I/O
OK
Diagnostics
Remedy
Green
•
Voltage supply for the binary inputs /
outputs is OK.
–
Off
•
Voltage supply for the binary inputs /
outputs is not applied.
1. Switch off the drive inverter in which the
MOVI-PLC
®
basic
DHP11B.. controller is
installed.
2. Check and correct the cabling of the
binary inputs / outputs according to
the electrical wiring diagram.
3. Check current consumption of the
connected actuators (max. current
Æ
Section 8).
4. Switch on the drive inverter in which the
MOVI-PLC
®
basic
DHP11B.. controller is
installed.
Orange
Voltage supply for the binary inputs/outputs is
applied. However, one of the following faults
has occurred:
•
Overload on one or several binary inputs /
outputs
•
Overtemperature of the output driver
•
Short circuit in at least one of the binary
inputs / outputs
Содержание MOVI-PLC basic DHP11B-T0
Страница 2: ...SEW EURODRIVE Driving the world ...
Страница 95: ...SEW EURODRIVE Driving the world ...