8
Technical data
Master module
Manual – MOVI-C
®
CONTROLLER advanced with PROFINET IO Fieldbus Interface
83
8.4
Master module
MOVI‑C
®
CONTROLLER advanced UHX45A /MDM90A
Electrical supply
•
Power consumption: P
max
= 972 W
•
Supply voltage V = DC 24 V (-15% / +20%)
according to IEC 61131‑2
•
Current consumption I
max
= 40.5 A
(with DC 24 V supply voltage)
X5_A
External DC 24 V supply voltage
(2-pin connection)
Connection type: Plug connector with strain relief
•
1 core: 0.5 mm
2
– 16 mm
2
•
2 cores: 0.25 mm
2
– 6 mm
2
(TWIN‑AEH
1)
)
Tightening torque: 1.7 – 1.8 Nm
X5_B
Output for the DC 24 V supply voltage
(2-pin connection)
Connection type: Plug connector via prefabricated connec-
tion
X5
Connection DC 24 V supply voltage
Connection type: CU bars 2 x 5 mm², M4 screw fitting
PE connection
Connection type: CU bar 3 × 14 mm², M6 screw fitting
XF
Safe DC 24 V supply voltage
Type: 5 x 20 mm glass tube, 4 A, 125 V, slow-blow
1) AEH: Conductor end sleeve
8.5
Technical data of the PROFINET interface
MOVI‑C
®
CONTROLLER advanced UHX45A
Manufacturer ID
010Ahex
Device ID
13dez
Connection technology
RJ45
Baud rate
100 MBd, full duplex
Network protocols
ARP, ICMP
Application protocols
PROFINET IO, HTTP, SNMP, SEW Application Services
Port numbers used
80, 161, 310, PROFINET DCE/RPC Ports (dynamic via end
point mapper)
Conformance class
C
Application profiles
PROFIsafe, PROFIenergy (in preparation)
Permitted cable types
Category 5 and higher, class D according to IEC 11801
Maximum cable length (switch to switch)
100 m
GSD file name
GSDML-Vx.yz-SEW-MOVI-C-CONTROLLER-UHX25-UHX45-
yyyymmdd-hhmmss
24777730/EN – 01/2018