![SEW-Eurodrive MOVI-C UHX45A Series Скачать руководство пользователя страница 21](http://html.mh-extra.com/html/sew-eurodrive/movi-c-uhx45a-series/movi-c-uhx45a-series_manual_1250103021.webp)
4
Installation notes
Mechanical installation
Manual – MOVI-C
®
CONTROLLER advanced with PROFINET IO Fieldbus Interface
21
4.2
Mechanical installation
CAUTION
Risk of injury to persons and damage to property.
Never install a defective or damaged MOVI-C
®
CONTROLLER.
•
Before installation, check the device for external damage. Replace any damaged
device.
NOTICE
Risk of damage to property due to mounting surface with poor conductivity.
Damage to the MOVI‑C
®
CONTROLLER.
•
The mounting plate in the control cabinet must be conductive over a large area
for the mounting surface of the MOVI‑C
®
CONTROLLER (metallically pure, good
conductivity). EMC‑compliant installation of the device can only be accomplished
with a mounting plate that is conductive over a large area.
NOTICE
Risk of damage to property due to non-compliance with the stipulated tightening
torques.
Damage to the MOVI‑C
®
CONTROLLER.
•
Always adhere to the stipulated tightening torques. Otherwise, excessive heat
can develop which would damage the device.
4.2.1
Minimum clearance and mounting position
MOVI‑C
®
CONTROLLER is installed in the control cabinet. Observe the following for
installation:
•
To ensure unobstructed cooling of the MOVI-C
®
CONTROLLER, leave a minimum
clearance of 100 mm above and below the device's housing. Make sure air circula-
tion in the clearance is not impaired by cables or other installation equipment.
•
Ensure
unobstructed
cooling
air
supply
and
make
sure
that
the
MOVI‑C
®
CONTROLLER is not exposed to the warm exhaust air from other
devices.
•
There is no need for clearance at the sides of the device. You may connect the
MOVI‑C
®
CONTROLLER and other devices (e.g. MOVIDRIVE
®
modular) in series.
•
Install the devices only vertically. You must not install them horizontally, tilted or
upside down.
24777730/EN – 01/2018